Application data

Basic definitions

Unit hand — When facing the supply air outlet from the front of the unit (air blowing in your face), your right hand will be the right hand side of the unit and your left hand the left hand side of the unit.

UNIT HAND

PIPING COMPONENTS

SYMBOL/SKETCH

DESCRIPTION

CV FACTOR

RATING*

1/2

3/4

PSI

F

 

 

 

MANUAL AIR VENT: Threaded brass needle valve

 

 

 

 

 

with screwdriver slot for adjustment.

 

 

 

 

 

Application — Body brazed into high point of heat-

N/A

N/A

400

100

 

ing and cooling coils for bleeding air from coil. Stan-

 

dard item on all hydronic coils (not used on steam

 

 

 

 

 

or DX coils). Should not be used in lieu of main sys-

 

 

 

 

 

tem air vents.

 

 

 

 

 

AUTOMATIC AIR VENT: Nickel plated brass valve,

 

 

 

 

 

fiber-disc type, with positive shut-off ballcheck and

 

 

 

 

 

quick vent feature via knurled vent screw.

 

 

 

 

 

Application — Optional replacement for manual air

 

 

 

 

 

vent. Automatically passes minute quantities of air

 

 

 

 

 

through the fiber discs which expand upon contact

N/A

N/A

125

240

 

with water, completely sealing the valve. As air

 

 

 

 

 

 

accumulates, the fiber discs dry and shrink, repeat-

 

 

 

 

 

ing the cycle. Not recommended for removing large

 

 

 

 

 

quantities of air encountered during initial start-up

 

 

 

 

 

or subsequent draining and refilling. Should not be

 

 

 

 

 

used in lieu of main system air vents.

 

 

 

 

 

SWAGE: Copper tube end expanded to accept a

 

 

 

 

 

copper tube of the same size for factory or field

 

 

 

 

 

brazing.

N/A

N/A

300

200

 

Application — Used where possible for all tubing

 

 

 

 

 

joints for best joint integrity.

 

 

 

 

 

CIRCUIT SETTER: Variable water flow balancing

 

 

 

 

 

valve with manual adjustment knob, pointer, per-

 

 

 

 

 

cent-open scale, memory stop and integral pres-

 

 

 

 

 

sure read-out ports.

2.12

3.9

300

250

 

Application — Used for close tolerance water flow

 

 

 

 

 

balancing. Positive shut-off ball valve feature allows

 

 

 

 

 

usage as combination balancing and shut-off valve.

 

 

 

 

 

 

 

 

 

 

LEGEND

Cv — Coefficient of Velocity

DX — Direct Expansion

*Check all system component pressure ratings (coils, values, pumps, etc.) with manufacturer and any applicable local or national piping codes prior to specifying system pressure rating.

19

Page 19
Image 19
Carrier 42BVC, 42BHC manual Application data, Basic definitions, Unit Hand Piping Components