Performance data (cont)

42BHC, BVC NOMINAL COOLING CAPACITIES

 

 

 

 

COOLING*

UNIT SIZE

NOMINAL

COIL

EWT

Total

Sensible

42BHC,BVC

CFM

ROWS

(F)

Capacity

Capacity

 

 

 

 

(MBtuh)

(MBtuh)

 

 

4

40

23.3

16.0

 

 

45

17.9

13.8

 

 

 

50

12.8

12.0

06

600

 

40

31.0

19.8

6

45

24.5

17.0

 

 

 

50

18.0

14.5

 

 

 

40

33.8

21.2

 

 

8

45

26.7

18.1

 

 

 

50

19.4

15.2

 

 

4

40

28.4

20.0

 

 

45

21.9

17.5

 

 

 

50

15.3

15.3

08

800

 

40

38.4

25.1

6

45

30.3

21.7

 

 

 

50

22.5

18.6

 

 

 

40

42.6

27.2

 

 

8

45

33.7

23.3

 

 

 

50

24.7

19.8

 

 

4

40

40.5

27.3

 

 

45

31.6

23.7

 

 

 

50

23.4

20.6

10

1000

 

40

52.2

33.3

6

45

41.7

28.7

 

 

 

50

31.2

24.5

 

 

 

40

57.7

36.0

 

 

8

45

46.4

31.0

 

 

 

50

34.6

26.2

 

 

 

40

45.4

31.2

 

 

4

45

35.5

27.2

 

 

 

50

26.5

23.8

12

 

 

40

59.6

38.4

1200

6

45

47.4

33.2

 

 

 

50

35.5

28.5

 

 

 

40

66.6

42.0

 

 

8

45

53.3

36.1

 

 

 

50

39.9

30.7

 

 

 

40

59.7

41.2

 

 

4

45

46.4

35.9

 

 

 

50

34.4

31.4

16

 

 

40

78.7

50.9

1600

6

45

62.6

44.1

 

 

 

50

46.8

37.8

 

 

 

40

89.0

56.0

 

 

8

45

71.3

48.3

 

 

 

50

53.3

41.0

 

 

 

40

75.2

51.6

 

 

4

45

59.0

45.1

 

 

 

50

44.1

39.5

20

 

 

40

99.0

63.8

2000

6

45

78.7

55.2

 

 

 

50

59.0

47.4

 

 

 

40

111.8

70.3

 

 

8

45

89.9

60.6

 

 

 

50

67.6

51.6

 

 

 

40

112.5

77.6

 

 

4

45

87.6

67.6

 

 

 

50

65.0

59.1

30

 

 

40

148.5

95.8

3000

6

45

117.8

82.8

 

 

 

50

88.1

71.1

 

 

 

40

168.0

105.5

 

 

8

45

135.0

91.0

 

 

 

50

101.2

77.4

 

 

 

40

157.7

106.7

 

 

4

45

123.6

92.9

 

 

 

50

92.6

81.1

40

 

 

40

204.0

130.5

4000

6

45

162.6

112.7

 

 

 

50

122.3

96.7

 

 

 

40

230.1

143.5

 

 

8

45

185.6

123.8

 

 

 

50

140.2

105.2

LEGEND

EWT — Entering Water Temperature

MBtuh — Capacity (Btuh in thousands)

*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10 degrees F.

NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning & Refrigeration Institute).

42BHC,BVC NOMINAL HEATING CAPACITIES

UNIT SIZE

NOMINAL CFM

ROWS

HEATING CAPACITY

42BHC,BVC

(MBtuh)

 

 

06

600

1

27.0

2

46.9

 

 

08

800

1

27.0

2

46.9

 

 

10

1000

1

27.0

2

46.9

 

 

12

1200

1

38.5

2

68.5

 

 

16

1600

1

48.0

2

87.7

 

 

20

2000

1

58.7

2

104.9

 

 

30

3000

1

78.0

2

149.2

 

 

40

4000

1

92.3

2

182.4

 

 

NOTES:

1.Ratings are based on 180 F Entering Water Temperature (EWT) and 70 F Entering Air Temperature (EAT).

2.Leaving-air temperature is not to exceed 104 F with the standard motor. Consult the factory for higher temperature motor applications.

3.For information on four and six-row heating coil capacities and applications, consult the factory.

4.For all application ratings, use the quick-selection ratings provided in this catalog, or contact the factory.