Performance data (cont)
42BHC, BVC NOMINAL COOLING CAPACITIES
| 
 | 
 | 
 | 
 | COOLING* | |
| UNIT SIZE | NOMINAL | COIL | EWT | Total | Sensible | 
| 42BHC,BVC | CFM | ROWS | (F) | Capacity | Capacity | 
| 
 | 
 | 
 | 
 | (MBtuh) | (MBtuh) | 
| 
 | 
 | 4 | 40 | 23.3 | 16.0 | 
| 
 | 
 | 45 | 17.9 | 13.8 | |
| 
 | 
 | 
 | 50 | 12.8 | 12.0 | 
| 06 | 600 | 
 | 40 | 31.0 | 19.8 | 
| 6 | 45 | 24.5 | 17.0 | ||
| 
 | 
 | 
 | 50 | 18.0 | 14.5 | 
| 
 | 
 | 
 | 40 | 33.8 | 21.2 | 
| 
 | 
 | 8 | 45 | 26.7 | 18.1 | 
| 
 | 
 | 
 | 50 | 19.4 | 15.2 | 
| 
 | 
 | 4 | 40 | 28.4 | 20.0 | 
| 
 | 
 | 45 | 21.9 | 17.5 | |
| 
 | 
 | 
 | 50 | 15.3 | 15.3 | 
| 08 | 800 | 
 | 40 | 38.4 | 25.1 | 
| 6 | 45 | 30.3 | 21.7 | ||
| 
 | 
 | 
 | 50 | 22.5 | 18.6 | 
| 
 | 
 | 
 | 40 | 42.6 | 27.2 | 
| 
 | 
 | 8 | 45 | 33.7 | 23.3 | 
| 
 | 
 | 
 | 50 | 24.7 | 19.8 | 
| 
 | 
 | 4 | 40 | 40.5 | 27.3 | 
| 
 | 
 | 45 | 31.6 | 23.7 | |
| 
 | 
 | 
 | 50 | 23.4 | 20.6 | 
| 10 | 1000 | 
 | 40 | 52.2 | 33.3 | 
| 6 | 45 | 41.7 | 28.7 | ||
| 
 | 
 | 
 | 50 | 31.2 | 24.5 | 
| 
 | 
 | 
 | 40 | 57.7 | 36.0 | 
| 
 | 
 | 8 | 45 | 46.4 | 31.0 | 
| 
 | 
 | 
 | 50 | 34.6 | 26.2 | 
| 
 | 
 | 
 | 40 | 45.4 | 31.2 | 
| 
 | 
 | 4 | 45 | 35.5 | 27.2 | 
| 
 | 
 | 
 | 50 | 26.5 | 23.8 | 
| 12 | 
 | 
 | 40 | 59.6 | 38.4 | 
| 1200 | 6 | 45 | 47.4 | 33.2 | |
| 
 | 
 | 
 | 50 | 35.5 | 28.5 | 
| 
 | 
 | 
 | 40 | 66.6 | 42.0 | 
| 
 | 
 | 8 | 45 | 53.3 | 36.1 | 
| 
 | 
 | 
 | 50 | 39.9 | 30.7 | 
| 
 | 
 | 
 | 40 | 59.7 | 41.2 | 
| 
 | 
 | 4 | 45 | 46.4 | 35.9 | 
| 
 | 
 | 
 | 50 | 34.4 | 31.4 | 
| 16 | 
 | 
 | 40 | 78.7 | 50.9 | 
| 1600 | 6 | 45 | 62.6 | 44.1 | |
| 
 | 
 | 
 | 50 | 46.8 | 37.8 | 
| 
 | 
 | 
 | 40 | 89.0 | 56.0 | 
| 
 | 
 | 8 | 45 | 71.3 | 48.3 | 
| 
 | 
 | 
 | 50 | 53.3 | 41.0 | 
| 
 | 
 | 
 | 40 | 75.2 | 51.6 | 
| 
 | 
 | 4 | 45 | 59.0 | 45.1 | 
| 
 | 
 | 
 | 50 | 44.1 | 39.5 | 
| 20 | 
 | 
 | 40 | 99.0 | 63.8 | 
| 2000 | 6 | 45 | 78.7 | 55.2 | |
| 
 | 
 | 
 | 50 | 59.0 | 47.4 | 
| 
 | 
 | 
 | 40 | 111.8 | 70.3 | 
| 
 | 
 | 8 | 45 | 89.9 | 60.6 | 
| 
 | 
 | 
 | 50 | 67.6 | 51.6 | 
| 
 | 
 | 
 | 40 | 112.5 | 77.6 | 
| 
 | 
 | 4 | 45 | 87.6 | 67.6 | 
| 
 | 
 | 
 | 50 | 65.0 | 59.1 | 
| 30 | 
 | 
 | 40 | 148.5 | 95.8 | 
| 3000 | 6 | 45 | 117.8 | 82.8 | |
| 
 | 
 | 
 | 50 | 88.1 | 71.1 | 
| 
 | 
 | 
 | 40 | 168.0 | 105.5 | 
| 
 | 
 | 8 | 45 | 135.0 | 91.0 | 
| 
 | 
 | 
 | 50 | 101.2 | 77.4 | 
| 
 | 
 | 
 | 40 | 157.7 | 106.7 | 
| 
 | 
 | 4 | 45 | 123.6 | 92.9 | 
| 
 | 
 | 
 | 50 | 92.6 | 81.1 | 
| 40 | 
 | 
 | 40 | 204.0 | 130.5 | 
| 4000 | 6 | 45 | 162.6 | 112.7 | |
| 
 | 
 | 
 | 50 | 122.3 | 96.7 | 
| 
 | 
 | 
 | 40 | 230.1 | 143.5 | 
| 
 | 
 | 8 | 45 | 185.6 | 123.8 | 
| 
 | 
 | 
 | 50 | 140.2 | 105.2 | 
LEGEND
EWT — Entering Water Temperature
MBtuh — Capacity (Btuh in thousands)
*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10 degrees F.
NOTE: All ratings at sea level. Ratings in accordance with ARI (Air Conditioning & Refrigeration Institute).
42BHC,BVC NOMINAL HEATING CAPACITIES
| UNIT SIZE | NOMINAL CFM | ROWS | HEATING CAPACITY | |
| 42BHC,BVC | (MBtuh) | |||
| 
 | 
 | |||
| 06 | 600 | 1 | 27.0 | |
| 2 | 46.9 | |||
| 
 | 
 | |||
| 08 | 800 | 1 | 27.0 | |
| 2 | 46.9 | |||
| 
 | 
 | |||
| 10 | 1000 | 1 | 27.0 | |
| 2 | 46.9 | |||
| 
 | 
 | |||
| 12 | 1200 | 1 | 38.5 | |
| 2 | 68.5 | |||
| 
 | 
 | |||
| 16 | 1600 | 1 | 48.0 | |
| 2 | 87.7 | |||
| 
 | 
 | |||
| 20 | 2000 | 1 | 58.7 | |
| 2 | 104.9 | |||
| 
 | 
 | |||
| 30 | 3000 | 1 | 78.0 | |
| 2 | 149.2 | |||
| 
 | 
 | |||
| 40 | 4000 | 1 | 92.3 | |
| 2 | 182.4 | |||
| 
 | 
 | 
NOTES:
1.Ratings are based on 180 F Entering Water Temperature (EWT) and 70 F Entering Air Temperature (EAT).
2.
3.For information on four and 
4.For all application ratings, use the 
24