Carrier 42BVC manual Performance data, 42BHC,BVC Airflow Correction Factors

Models: 42BHC 42BVC

1 40
Download 40 pages 30.97 Kb
Page 23
Image 23

Performance data

42BHC,BVC AIRFLOW CORRECTION FACTORS

CFM RATIO

TOTAL (Ct)

SENSIBLE (Cs)

(Actual/Base)

 

 

1.40

1.25

1.26

1.35

1.22

1.23

1.30

1.19

1.20

1.25

1.16

1.17

1.20

1.13

1.14

1.15

1.10

1.11

1.10

1.07

1.08

1.05

1.04

1.04

1.00

1.00

1.00

0.95

0.97

0.97

0.90

0.94

0.93

0.85

0.90

0.89

0.80

0.86

0.85

0.75

0.82

0.81

0.70

0.78

0.77

0.65

0.74

0.72

0.60

0.70

0.67

0.55

0.66

0.62

0.50

0.62

0.57

0.45

0.58

0.52

0.40

0.53

0.47

0.35

0.48

0.42

0.30

0.43

0.38

0.25

0.38

0.33

NOTE: Use Sensible Heat correction factors when calculating heating capacity.

DIRECT EXPANSION (DX) CORRECTION FACTORS

% OF

CORRECTION FACTOR

NOMINAL CFM

Total

Sensible

80

0.95

0.93

90

0.97

0.96

100

1.00

1.00

110

1.02

1.04

120

1.05

1.08

Consult factory for values outside of table.

DX Total Capacity (MBtuh) = Base Et x Total Correction Factor

DX Sensible Capacity (MBtuh) = Base Es x Sensible Correction Factor

%of Nominal Cfm = Actual Cfm (from Fan Performance table) ÷ Nominal Cfm

ALTITUDE COOLING CORRECTION FACTORS

ELEVATION (ft)

TOTAL HEAT (Et)

SENSIBLE HEAT (Es)

1000

0.99

0.96

2000

0.98

0.93

3000

0.97

0.89

4000

0.96

0.86

5000

0.94

0.83

6000

0.93

0.80

7000

0.92

0.77

8000

0.91

0.75

9000

0.90

0.73

42BHC,BVC HOT WATER CAPACITY CORRECTION FACTORS

ENTERING AIR

 

 

 

ENTERING WATER TEMPERATURE (F)

 

 

 

TEMPERATURE (F)

100

110

120

130

140

150

160

170

180

190

200

50

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

1.273

1.364

55

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

1.227

1.318

60

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

1.273

65

0.318

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

1.227

70

0.272

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

1.182

75

0.227

0.318

0.409

0.500

0.591

0.682

0.773

0.864

0.955

1.045

1.136

80

0.182

0.272

0.363

0.455

0.545

0.636

0.727

0.818

0.909

1.000

1.091

NOTES:

1.Leaving air temperature not to exceed 104 F with standard motor.

2.Base capacity ratings based on 180 F entering water temperature and 70 F entering air temperature.

3.Hot Water Heating Capacity (MBtuh) = Rated Heating Capacity x Hot Water Capacity Correction Factor x Sensible Airflow Correc- tion Factor.

23

Page 23
Image 23
Carrier 42BVC manual Performance data, 42BHC,BVC Airflow Correction Factors, Direct Expansion DX Correction Factors