 CAUTION - NOTICE TO RIGGERS:

ALL PANELS MUST BE IN PLACE WHEN RIGGING. CAUTION - NOTICE TO RIGGERS:

ALL PANELS MUST BE IN PLACE WHEN RIGGING.

NOTE: Rig with four cables and spread with two 92 inch (2337 MM) spreader bars. Maintain a distance of 74 inches (1880 MM) from top of unit to eyehook.

16

CENTER

OF

GRAVITY

a48-8246

BC

A

UNIT

WEIGHT

 

A

 

B

 

C

 

LB

KG

INCHES

MM

INCHES

MM

INCHES

MM

50AJ/AK020

4607

2090

87.7

2227

70.9

1801

42.0

1067

48AJ/AKD020

4697

2131

87.7

2227

71.9

1826

42.5

1080

48AJ/AKE020

4777

2167

87.7

2227

72.8

1849

41.0

1041

50AW/AY020

4685

2125

87.7

2227

70.9

1801

42.0

1067

48AW/AYD020

4737

2149

87.7

2227

71.9

1826

42.5

1080

48AW/AYE020

4817

2185

87.7

2227

72.8

1849

41.0

1041

50AJ/AK025

4680

2123

87.7

2227

68.0

1727

43.9

1115

48AJ/AKD025

4770

2164

87.7

2227

69.1

1755

44.3

1125

48AJ/AKE025

4850

2200

87.7

2227

69.6

1768

44.6

1133

50AW/AY025

4758

2158

87.7

2227

68.0

1727

43.9

1115

48AW/AYD025

4810

2182

87.7

2227

69.1

1755

44.3

1125

48AW/AYE025

4890

2218

87.7

2227

69.6

1768

44.6

1133

50AJ/AK027

4873

2210

87.7

2227

68.0

1727

43.9

1115

48AJ/AKD027

4963

2251

87.7

2227

69.1

1755

44.3

1125

48AJ/AKE027

5043

2287

87.7

2227

69.6

1768

44.6

1133

50AW/AY027

4951

2246

87.7

2227

68.0

1727

43.9

1115

48AW/AYD027

5003

2269

87.7

2227

69.1

1755

44.3

1125

48AW/AYE027

5083

2306

87.7

2227

69.6

1768

44.6

1133

50AJ/AK030

5023

2278

87.7

2227

68.0

1727

43.6

1107

48AJ/AKD030

5113

2319

87.7

2227

69.1

1755

44.0

1118

48AJ/AKE030

5193

2356

87.7

2227

69.6

1768

44.3

1125

50AW/AY030

5101

2314

87.7

2227

68.0

1727

43.6

1107

48AW/AYD030

5153

2337

87.7

2227

69.1

1755

44.0

1118

48AW/AYE030

5233

2374

87.7

2227

69.6

1768

44.3

1125

50AJ/AK035

5229

2372

87.7

2227

68.3

1735

46.5

1181

48AJ/AKD035

5434

2465

87.7

2227

69.4

1763

46.9

1191

48AJ/AKE035

5594

2537

87.7

2227

70.0

1778

47.2

1199

50AW/AY035

5422

2459

87.7

2227

68.3

1735

46.5

1181

48AW/AYD035

5474

2483

87.7

2227

69.4

1763

46.9

1191

48AW/AYE035

5634

2556

87.7

2227

70.0

1778

47.2

1199

50AJ/AK036

5609

2544

87.7

2227

93.4

2372

45.3

1152

48AJ/AKD036

5814

2637

87.7

2227

94.8

2409

45.8

1163

48AJ/AKE036

5974

2710

87.7

2227

96.3

2446

46.1

1172

50AW/AY036

5802

2632

87.7

2227

93.3

2370

45.4

1153

48AW/AYD036

5854

2655

87.7

2227

94.8

2408

45.8

1163

48AW/AYE036

6014

2728

87.7

2227

96.3

2446

46.1

1172

50AJ/AK040

5769

2617

87.7

2227

90.8

2306

46.5

1181

48AJ/AKD040

5974

2710

87.7

2227

92.3

2344

46.9

1191

48AJ/AKE040

6134

2782

87.7

2227

93.8

2383

47.2

1199

50AW/AY040

5962

2704

87.7

2227

90.8

2306

46.5

1181

48AW/AYD040

6014

2728

87.7

2227

92.3

2344

46.9

1191

48AW/AYE040

6174

2801

87.7

2227

93.8

2383

47.2

1199

50AJ/AK041

5885

2669

87.7

2227

89.0

2261

45.6

1158

48AJ/AKD041

6090

2762

87.7

2227

90.5

2300

46.0

1169

48AJ/AKE041

6250

2835

87.7

2227

92.1

2338

46.3

1177

50AW/AY041

6078

2757

87.7

2227

89.1

2262

45.6

1159

48AW/AYD041

6130

2781

87.7

2227

90.6

2300

46.0

1169

48AW/AYE041

6290

2853

87.7

2227

92.1

2339

46.3

1177

50AJ/AK050

6338

2875

87.7

2227

89.2

2266

46.1

1171

48AJ/AKD050

6543

2968

87.7

2227

90.7

2304

46.5

1181

48AJ/AKE050

6703

3040

87.7

2227

92.2

2342

46.8

1189

50AW/AY050

6531

2962

87.7

2227

89.2

2266

46.1

1171

48AW/AYD050

6583

2986

87.7

2227

90.7

2304

46.5

1181

48AW/AYE050

6743

3059

87.7

2227

92.2

2342

46.8

1189

NOTE:

Add 312 lb (142 kg) for export crating. (020-035 units) Add 346 lb (157 kg) for export crating. (036-050 units) Add 588 lb (266 kg) for export crating. (051 and 060 units) Add 220 lb (100 kg) for copper condenser coil. (020-035 units) Add 380 lb (172 kg) for copper condenser coil. (036-050 units)

Add 651 lb (295 kg) for copper condenser coil. (051 and 060 units)

50AJ/AK051

8544

3876

161.7

4106

126.0

3200

44.6

1133

48AJ/AKD051

8674

3935

161.7

4106

133.2

3383

46.6

1185

48AJ/AKE051

8914

4043

161.7

4106

140.2

3562

48.7

1237

50AW/AY051

8759

3973

161.7

4106

125.9

3198

44.6

1133

48AW/AYD051

8714

3953

161.7

4106

133.2

3382

46.6

1185

48AW/AYE051

8964

4066

161.7

4106

140.2

3562

48.7

1237

50AJ/AK060

8708

3950

161.7

4106

123.6

3139

44.6

1133

48AJ/AKD060

8838

4009

161.7

4106

130.7

3320

46.6

1184

48AJ/AKE060

9078

4118

161.7

4106

137.7

3498

48.6

1234

50AW/AY060

8923

4047

161.7

4106

123.6

3139

44.6

1133

48AW/AYD060

8878

4027

161.7

4106

130.7

3320

46.6

1184

48AW/AYE060

9128

4140

161.7

4106

137.7

3498

48.6

1234

Fig. 11 — Rigging Information