building, route the high tap to atmosphere and the low tap to building air.
Step 12 — Install All Accessories — After all the
The 48A Series units have a large number of factory- installed options which were previously available only as accessories. Some of the available options can also be installed in the field if needed. In most cases the units have been
•Thermostats and space temperature sensors
•LP (liquid propane) conversion kit
•Accessory barometric relief damper
•Accessory power exhaust
•
•Condenser coil hail guards
•Outdoor humidity sensor (used for economizer enthalpy changeover)
•Return air humidity sensors (used for economizer differential enthalpy changeover)
•Return air smoke detector
•Controls expansion module (used for interface to build- ing management systems, not typically needed on system with the Carrier Comfort Network® [CCN] sys- tem)
•Plugged filter sensor
•Motormaster® V low ambient head pressure control
IMPORTANT: Carrier recommends the installation of
Step 13 — Field Modifications
DUCTWORK
Bottom Return Units (48AJ and AK)
IMPORTANT: The following section is a guideline and not a comprehensive procedure to field modify the units. The installing contractor must provide some design initiative.
Conversion to horizontal return requires that the bottom return openings of the unit must be sealed with airtight panels
capable of supporting the weight of a person. The return ductwork connection locations on the side of the unit are higher than normal
To convert the unit, perform the following:
1.Seal the bottom return openings of the unit with airtight panels capable of supporting the weight of a person.
2.Remove the panels located below the economizer
3.Run the return air ductwork up to the openings. One single duct is recommended to connect to the unit over the return air openings. See Fig. 34. The return duct must incorporate a minimum
Side Supply and Return Units (48AW,AY) with Field- Installed Power Exhaust in Return Duct — Space must be available in the return duct to mount the power exhaust fan (gravity relief) modules. Dimensions and suggested locations are shown in Fig. 34. These instructions are a guideline and not a comprehensive procedure. The design contractor must pro- vide some design initiative.
The wiring harness that is provided with the power exhaust accessory is not long enough for the fan modules to be mount- ed in the return air duct.
AUXILIARY | PRESSURE TRANSDUCERS | ||
CONTROL BOX | (INSIDE OF PANEL) | ||
|
Fig. 33 — Pressure Transducer Locations
35