Carrier 48AJ Make Electrical Connections, Field Gas Piping, 48A Series Staged Gas Control

Models: 48AJ

1 36
Download 36 pages 38.76 Kb
Page 20
Image 20
Fig. 18 — Field Gas Piping

a48-2524

Fig. 18 — Field Gas Piping

IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

OPTIONAL STAGED GAS UNITS — See Table 7 for staged gas information. Staging pattern is selected during controls start-up.

For complete information and service instructions for Staged Gas Control Units, see Control Operation and Trouble- shooting literature.

Table 7 — 48A Series Staged Gas Control

MODEL NUMBER POSITION

NUMBER OF

HEAT SIZE

5

6,7,8

STAGES

 

 

020

 

 

 

025

 

 

 

027

 

 

 

030

 

 

S

035

 

Low

 

036

 

 

 

040

5 stages

 

 

041

 

 

050

 

 

 

035

 

 

 

036

 

 

T

040

 

High

 

041

 

 

 

050

 

 

 

020

 

 

T

025

7 stages

High

027

 

 

 

 

030

 

 

T

051,060

9 stages

High

S

051,060

11 stages

Low

Step 8 — Make Electrical Connections

POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate.

Provide a unit safety disconnect switch in the main power supply to each unit (see Fig. 19). Select switch size and mount- ing location in accordance with applicable local codes or National Electrical Code (NEC). If combining the functions of safety disconnect with maximum overcurrent protection (MOCP) fuses (“fused disconnect”), coordinate safety switch size with MOCP size data as marked on unit informative plate.

Unit may be equipped with optional factory-installed non- fused disconnect switch (see Fig. 19). Provide maximum overcurrent protection devices (fuses or HACR breakers, per

local codes) in branch circuit wiring remote from unit. Observe requirements of NEC Article 440. Install service switch upstream of remote fuses if required.

The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 19. Units have circuit breakers for compressors, fan motors, and control circuit. The unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI C1-latest year.

FIELD POWER SUPPLY — Unit is factory wired for volt- age shown on unit nameplate. See Tables 8A and 8B for elec- trical data.

Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (corner post next to control box).

A 31/2-in. NPT coupling for field power wiring and a 3/4-in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 21/2-in. (48A020-035) or 3-in. (48A036-060) knockouts for the field power wiring. See Fig. 4-9. If control wiring is to be brought in through the side of unit, a 7/8-in. diameter hole is provided in the condenser side post next to the control box.

Do not route control wiring in the same conduit as power wiring.

If disconnect box is mounted to corner post, be careful not to drill or screw into the condenser coil.

 

 

 

TB1

 

 

FIELD

21

 

PERDISCONNECTNEC

11

SUPPLIEDFIELD

POWER

22

12

 

 

 

 

SUPPLY

23

 

 

13

 

 

EQUIP GND

 

 

FIELD-INSTALLED DISCONNECT

 

 

 

OPTIONAL

 

 

FACTORY-INSTALLED

 

 

DISCONNECT

WIRING

11

21

12

22

POWERFIELD

13

23

 

 

 

 

GND

 

 

FACTORY-INSTALLED DISCONNECT

a48-6977

LEGEND

GND — Ground

NEC — National Electrical Code

TB — Terminal Block

Fig. 19 — Field Power Wiring Connections

20

Page 20
Image 20
Carrier 48AJ Make Electrical Connections, Field Gas Piping, 48A Series Staged Gas Control, Field Power Wiring Connections