Check Gas Input

integrated gas unit controller (IGC) has the capability to automatically reduce the evaporator “ON” delay and in- crease the evaporator “OFF” delay in the event of high duct static and/or partially-clogged filter.

Check Gas Input

Check gas input and manifold pressure after unit start-up (See Table 3). If adjustment is required proceed as follows:

SThe rated gas inputs shown in Table 3 are for altitudes from sea level to 2000 ft (610 m) above sea level. These inputs are based on natural gas with a heating value of 1025 Btu/ft3 at 0.60 specific gravity, or propane gas with a heating value of 2500 Btu/ft3 at 1.5 specific gravity.

IN THE U.S.A.:

The input rating for altitudes above 2,000 ft (610 m) must be reduced by 4% for each 1,000 ft (305 m) above sea level.

For installations below 2,000 ft (610 m), refer to the unit rating plate.

For installations above 2,000 ft (610 m) multiply the input by on the rating plate by the derate multiplier in Table 4 for correct input rate.

Table 4 – Altitude Derate Multiplier for U.S.A.*

ALTITUDE FT (M)

PERCENT OF DERATE

DERATE MULTIPLIER

FACTOR{

 

 

 

 

 

 

0---2000

0

1.00

(0---610)

 

 

 

 

 

2001---3000*

8--- 12

0.90

(610

---914)

 

 

 

 

 

 

3001

---4000

12--- 16

0.86

(315---1219)

 

 

 

 

 

 

4001

---5000

16--- 20

0.82

(1220

---1524)

 

 

 

 

 

 

5001

---6000

20--- 24

0.78

(1524

---1829)

 

 

 

 

 

 

6001

---7000

24--- 28

0.74

(1829

---2134)

 

 

 

 

 

 

7001

---8000

28--- 32

0.70

(2134

---2438)

 

 

 

 

 

 

8001

---9000

32--- 36

0.66

(2439

---2743)

 

 

 

 

 

9001---10,000

36--- 40

0.62

(2744

---3048)

 

 

*In Canada see Canadian Altitude Adjustment.

{Derate multiplier factors are based on midpoint altitude for altitude range.

BURNER FLAME

BURNER

MANIFOLD

C99021

Fig. 10 - Monoport Burner

IN CANADA:

The input rating for altitudes from 2,000 to 4,500 ft (610 m to 1372 m) above sea level must be derated 10% by an authorized Gas Conversion Station or Dealer.

EXAMPLE:

90,000 Btu/hr Input Furnace Installed at 4300 ft (1311 m).

Furnace Input Rate at

X

Derate Multiplier

=

Furnace Input Rate at

Sea Level

 

Factor

 

Installation Altitude

90,000

X

0.90

=

81,000

When the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size.

 

!

CAUTION

 

 

 

 

 

 

 

 

 

 

 

UNIT DAMAGE HAZARD

 

 

 

Failure to follow this caution may result in reduced unit

 

 

 

 

 

and/or component life.

 

 

 

 

 

Do Not redrill

an orifice. Improper drilling (burrs,

 

 

 

 

 

out-of-round holes, etc.) can cause excessive burner noise

 

 

 

 

 

and misdirection of burner flame. If orifice hole appears

 

 

 

 

 

damaged or it is suspected to have been redrilled, check

 

 

 

 

 

orifice hole with a numbered drill bit of correct size.

 

 

 

 

 

 

 

 

 

 

Adjust Gas Input

 

 

 

 

The gas input to the unit is determined by measuring the gas flow

 

at the meter or by measuring the manifold pressure. Measuring the

 

gas flow at the meter is recommended for natural gas units. The

 

A

manifold pressure must be measured to determine the input of

--

propane gas units.

 

 

 

 

 

 

48EZ

Measure Gas Flow (Natural Gas Units)

 

Minor adjustment to the gas flow can be made by changing the

 

manifold pressure. The manifold pressure must be maintained

 

between 3.2 and 3.8 IN. W.C.

 

If larger adjustments are required, change main burner orifices

 

following the recommendations of national and local codes.

 

NOTE: All other appliances that use the same meter must be

 

turned off when gas flow is measured at the meter.

 

Proceed as follows:

 

 

 

 

1.Turn off gas supply to unit.

2.Remove pipe plug on manifold (See Fig. 11) and connect manometer. Turn on gas supply to unit.

3.Record number of seconds for gas meter test dial to make one revolution.

4.Divide number of seconds in Step 3 into 3600 (number of seconds in one hr).

Pipe Plug

Manifold

 

A07679

Fig. 11 - Burner Assembly

5.Multiply result of Step 4 by the number of cubic feet (cu ft) shown for one revolution of test dial to obtain cubic feet (cu ft) of gas flow per hour.