location is ideal for the maintenance technician, and five access panels, easily removed, provide quick and convenient access to all components when needed. As an added plus, all required service/ maintenance access can be from one side allowing the unit to be located against a wall or ceiling plenum obstruc- tion, an obvious space-saving idea.

Carrier quality and reliability

The Carrier 50AH ROOMTOP® units have much to offer the cost- and efficiency-conscious commercial owner. Every unit is thoroughly run tested at the factory and equipped with safety controls designed to monitor and protect over the life of the unit.

Scroll compressor technology

Scroll compressors are designed for high efficiency and are internally spring mounted to minimize vibration noise. Each compressor is hermetically sealed against contamination to promote longer life and dependable operation. Scroll compressors are standard on all units.

Table of contents

Page

Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2

Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

ARI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10

Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11,12

Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15

Quality Assurance

I

 

®

 

 

 

 

5

O

 

 

 

 

 

 

 

 

 

 

 

 

2

S

 

 

 

 

 

3

 

9

 

 

 

 

2

 

0

 

 

A

 

 

 

0

1:2

000

#

 

 

 

 

 

 

 

 

 

Model number nomenclature

50AH – 048 – M – 5 4 1 XX

Model Designation –

50AH Horizontal,

Indoor Single-Package

Cooling Unit

Nominal Tons

 

 

024

2

048

4

036

3

060

5

Indoor Fan Motor

– – Standard Motor

M – 1.5 hp Optional Motor

FIOP*

Packaging

1– Domestic

2– Export

Design Revision

Voltage

6 – 460-3-60

3

230-1-60

5

208/230-3-60

 

*FIOP — Factory-Installed option, contact your Carrier representative for details.

ARI* capacity ratings

UNIT

V-PH-Hz

TOTAL

NET TOTAL

NOMINAL

EER

SEER

SEER

SOUND RATING

50AH

kW

COOLING CAP. (Btuh)

CFM

(with TDR)

(dB)

 

 

 

024

230-1-60

2.56

24,800

800

10.50†

78

036

230-1-60

 

 

 

10.00

10.00

 

208/230-3-60

4.3

36,000

1200

8.40

82

 

460-3-60

 

 

 

8.40

 

048

230-1-60

 

 

 

10.00†

 

208/230-3-60

5.63

49,500

1600

8.80

82

 

460-3-60

 

 

 

8.80

 

060

230-1-60

 

 

 

9.70

10.00

 

208/230-3-60

6.9

58,500

2000

8.50

82

 

460-3-60

 

 

 

8.50

 

dB

LEGEND

Decibels

EER

Energy Efficiency Ratio

SEER —

Seasonal Energy Efficiency Ratio

TDR

Time-Delay Relay

*Air-conditioning and Refrigeration Institute. †TDR is standard.

NOTES:

1.Ratings are at zero condenser air static and rated in accordance with ARI Standard 210.

NET CAPACITY (Btuh)

2. EER =

TOTAL WATTS

2

Page 2
Image 2
Carrier 50AH manual Table of contents, Model number nomenclature, ARI* capacity ratings