Carrier Electric Heater Data, Electric Heater Used with, Branch Circuit Unit 88EN Unit 50AH

Models: 50AH

1 16
Download 16 pages 19.09 Kb
Page 10
Image 10

Electrical data (cont)

ELECTRIC HEATER DATA

ELECTRIC HEATER

USED WITH

V-PH

CAP. (kW)

 

BRANCH CIRCUIT

 

UNIT 88EN

UNIT 50AH

(60 Hz)

Heater Amps

MCA

 

MOCP (Amps)

 

 

0050CA01

 

240-1

5.0

20.8

26.0

 

30

0075CA01

 

240-1

7.5

31.3

39.1

 

40

0115CA01

024, 036

240-1

11.5

47.9

59.9

 

60

0075EA01

1-Stage Heat

208-3

5.6

15.6

19.5

 

20

 

240-3

7.6

18.0

22.6

 

25

 

 

 

1150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-3

15.0

36.1

45.1

 

50

 

 

 

0100EA01

 

208-3

7.5

20.8

26.0

 

30

 

240-1*

10.0

41.7

52.1

 

60

 

 

240-3

10.0

24.1

30.1

 

35

0150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-1*

15.0

62.5

78.1

 

80

 

 

240-3

15.0

36.1

45.1

 

50

0200EA01

 

208-3

15.0

41.7

52.1

 

60

048, 060

240-1*

20.0

83.3

104.2

 

110

 

2-Stage Heat

240-3

20.0

46.9

58.6

 

60

0300EA01

 

208-3

22.5

62.5

78.2

 

80

 

240-3

30.0

72.2

90.2

 

100

 

 

 

0300CA01

 

240-1

30.0

124.0

155.0

 

175

0100FA01

 

480-3

10.0

12.0

15.0

 

15

0150FA01

 

480-3

15.0

18.1

22.6

 

25

0200FA01

 

480-3

20.0

24.1

30.1

 

35

0300FA01

 

480-3

30.0

36.1

45.1

 

50

LEGEND

MCA — Minimum Circuit Ampacity

MOCP — Maximum Overcurrent Circuit Protection

(Fuses or Circuit Breaker)

*May be field converted to single-phase units, see electric heat installation instructions. NOTE: Separate power source is required for all heaters. Control from base unit 50AH (24 v).