TROUBLESHOOTING

See Table 13 for troubleshooting information.

Table 13 — ERV Troubleshooting

SYMPTOM

POSSIBLE CAUSES

ACTION TO CHECK

POSSIBLE REMEDY

 

Disconnect switch is in the off

Verify that the disconnect switch is

Move the disconnect lever to the 'ON'

 

position

in the 'ON' position

position.

 

 

 

Using a volt meter verify that the voltage

 

No power to the ERV

Check for power at the disconnect

being supplied to the ERV matches the ERV's

 

switch

operating voltage. If the ERV operates on

 

 

 

 

 

three phase power check all three legs.

ERV will not turn on

 

 

Using a volt meter verify that the voltage on

 

One or more blown fuses

Check for power at the bottom of

the bottom side of the fuse block matches the

 

the fuse block

ERV's operating voltage. If the ERV operates

 

 

 

 

 

on three phase power check all three legs.

 

Control board transformer circuit

Look at the small transformer next

 

 

to the control circuit board to see if

Depress the circuit breaker back in.

 

breaker is tripped

 

the black circuit pushed out

 

 

 

 

 

The fan speed / CFM level is set

Use the user interface push button

Adjust the fan speed / CFM demand levels by

 

to view the 'Outside Air' and

pressing the user interface push button and

 

too low

 

'Exhaust Air' settings

turning the adjust knob.

 

 

 

 

 

Using a volt meter verify that the voltage on

 

One or more blown fuses

Check for power at the bottom of

the bottom side of the fuse block matches the

 

the fuse block

ERV's operating voltage. If the ERV operates

 

 

 

 

 

on three phase power check all three legs.

 

Rooftop Economizer Option (if

 

Using a continuity meter check for continuity

 

Check for continuity across the

across the two wires that connect to the mer-

ERV is running but

equipped) has shut down the ERV

mercury switch on the economizer

cury switch on the economizer damper. If the

blowers will not turn

because the rooftop unit is in 'Free

damper.

contacts are open, the rooftop unit is in 'Free

 

Cooling' mode

 

Cooling'.

 

 

 

 

Smoke Detector Option (if

 

Using the wiring schematics verify that the

 

equipped) has shut down the ERV

 

 

Check for wiring errors.

smoke detector is wired to the control board

 

because it is sensing smoke in the

 

properly.

 

exhaust airstream on the ERV.

 

 

 

 

 

 

Check to see if the outside temper-

Use a thermometer to measure the outside

 

Low Temperature Lockout Option

temperature. Use the wiring schematics to

 

(if equipped)

ature is above –30 F

verify that temperature probe on the intake air

 

(–34.4 C). Check for wiring errors

 

 

side of the ERV is wired properly.

 

 

 

 

The fan speed / CFM level is set

Use the user interface push button

Adjust the fan speed / CFM demand levels by

 

to view the 'Outside Air' and

pressing the user interface push button and

 

too low

 

'Exhaust Air' settings

turning the adjust knob.

 

 

 

Rooftop Economizer with Power

 

Using a continuity meter check for continuity

 

Relief Option (if equipped) has

Check for continuity across the

across the two wires that connect to the mer-

 

shut down the supply blower

mercury switch on the economizer

cury switch on the economizer damper. If the

Only one of the two

because the rooftop unit is in 'Free

damper

contacts are open, the rooftop unit is in 'Free

blowers is turning

Cooling' mode

 

Cooling'.

 

One of the blowers is wired

 

Using the wiring schematics verify that both

 

Check for wiring errors.

the power wires and the control wires are con-

 

incorrectly

 

 

nect properly.

 

 

 

 

The ERV Standard Frost Protec-

 

 

 

tion Option has turned off the sup-

Check for frost on the wheel.

Wait for Defrost mode to finish.

 

ply blower to defrost the wheel

 

 

 

The ERV Enthalpy Control, Dry

 

 

 

bulb Control / Wheel Bypass Stop /

Check for Stop / Jog movement of

Wait until sequence is completed.

 

Jog Option (if equipped) is

wheel.

 

 

 

activated

 

 

 

 

Check to see if the connector

 

 

The wheel motor is unplugged.

between the wheel motor and the

Plug the two connectors together.

 

cabinet wiring is securely

 

 

 

Blowers are on but

 

connected.

 

The wheel motor is wired

 

Compare the wheel motor, control board and

the wheel is not

Check for wiring errors.

incorrectly.

relay are wired correctly.

turning

 

The wheel belt is off or broken

Check the wheel belt.

Verify that the wheel belt is seated in the pul-

 

 

ley and on the rim of the wheel.

 

 

 

 

 

 

Carefully rotate the wheel by grabbing the

 

 

 

outer rim and spinnig the wheel. After letting

 

The air seals on the wheel are too

Check to see if the wheel spins

go the wheel should continue to spin for three

 

tight

freely.

to four seconds. Should the air seals need

 

 

 

adjusting see the maintainence section of this

 

 

 

book.

Copyright 2010 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53620007-01

Printed in U.S.A.

Form 62E-C1SI

Pg 38

8-10

Replaces: New

Page 38
Image 38
Carrier 62E specifications ERV Troubleshooting, Symptom Possible Causes Action to Check Possible Remedy

62E specifications

The Carrier 62E is a highly regarded air conditioning unit known for its efficiency, reliability, and advanced technology features. Designed to cater to both residential and light commercial applications, this model is recognized for its ability to provide optimal cooling performance even in challenging climates.

One of the standout features of the Carrier 62E is its energy efficiency. The unit boasts a high Seasonal Energy Efficiency Ratio (SEER) rating, which ensures significant energy savings over time. This efficiency not only translates to lower energy bills for users but also contributes positively to environmental sustainability. The Carrier 62E is designed with eco-friendly refrigerants that minimize its carbon footprint while maintaining high performance levels.

In terms of technology, the Carrier 62E comes equipped with innovative smart controls. The unit can be integrated with smart home systems, allowing users to control their cooling preferences through their smartphones or other connected devices. This feature enhances convenience, enabling homeowners to adjust temperatures and monitor their system remotely, ensuring maximum comfort regardless of their location.

The 62E is engineered with a durable and robust build, ensuring long-lasting reliability. The components are crafted to withstand harsh weather conditions, making it a solid investment for users in varied climates. Additionally, the unit operates quietly, thanks to its advanced sound-dampening technologies, ensuring that indoor environments remain peaceful and undisturbed.

Installation of the Carrier 62E is straightforward, thanks to its versatile design and flexibility. The system can be configured for various ductwork arrangements, adapting seamlessly to different home layouts and existing infrastructure.

Another notable characteristic of the Carrier 62E is its advanced filtration system. The unit comes with a high-efficiency filter that captures airborne particles, allergens, and pollutants, promoting cleaner and healthier indoor air quality. This is an essential feature for households with allergy sufferers, as it helps create a more comfortable living space.

Overall, the Carrier 62E stands out as a leader in residential and light commercial air conditioning solutions. With its energy efficiency, state-of-the-art technology, durable design, and air quality improvements, it meets the diverse needs of modern users while providing remarkable comfort throughout the year. As climate considerations become increasingly important, the Carrier 62E remains a compelling choice for those seeking to enhance their home's comfort while being mindful of energy consumption and environmental impact.