Table 1A — Physical Data — SI (cont)
UNIT 62E | LD |
| LG | MD |
| MG | ND |
| NG | PD |
| PG | |
NOMINAL CAPACITY (L/s) | 3585 |
| 4340 | 2830 |
| 5100 | 5200 |
| 6500 | 5950 |
| 7080 | |
CAPACITY RANGE (L/s) |
|
|
|
| |||||||||
MAXIMUM SHIPPING | 1232 |
| 1308 | 1397 |
| 1397 | 1482 |
| 1482 | 1533 |
| 1608 | |
WEIGHT (kg) |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
MAXIMUM OPERATING | 1118 |
| 1194 | 1283 |
| 1283 | 1368 |
| 1368 | 1420 |
| 1495 | |
WEIGHT (kg) |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
UNIT DIMENSIONS (mm) |
|
|
|
|
|
|
|
|
|
|
|
| |
Length (includes hoods) | 2355 | 2532 | 2685 | 2812 | |||||||||
Width | 2162 | 2339 | 2492 | 2619 | |||||||||
Height | 1687 | 1712 | 1737 | 1824 | |||||||||
ROTARY ENERGY |
|
|
|
|
|
|
|
|
|
|
|
| |
EXCHANGER |
|
|
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
|
|
| Segmented |
|
|
|
|
| ||
Size (Diam x Depth) (mm) | 1727 x 76 | 1880 x 76 | 2057 x 76 | 2184 x 76 | |||||||||
Nominal Drive Motor kW |
| 0.2 |
| 0.2 |
| 0.2 |
| 0.2 | |||||
SUPPLY/EXHAUST FANS |
|
|
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
| Backward Inclined, Single Width Single Inlet |
|
|
| ||||||
Drive Type |
|
|
| EC Motor with Integral Frequency Drive |
|
|
| ||||||
Fan Option Code | F, G, L, M |
| F, G, M | F, G, M | F, G, M |
| G, M | F, G, M |
| G, M | |||
(see fan option table) |
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
FILTERS |
|
|
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
|
|
| 51 mm Pleated |
|
|
|
|
| ||
Exhaust Air – Qty...Size | 6…406 x 635 x 51 | 6…457 x 635 x 51 | 6…508 x 508 x 51 | 8…508 x 610 x 51 | |||||||||
(L x W x D) (mm) | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
Outside Air – Qty...Size | 6…406 x 635 x 51 | 6…457 x 635 x 51 | 6…508 x 508 x 51 | 8…508 x 610 x 51 | |||||||||
(L x W x D) (mm) | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
UNIT 62E | RD |
| RG | SD |
| SG | TD | TG | UD | UG | |
NOMINAL CAPACITY (L/s) | 6500 |
| 8000 | 7800 |
| 9400 | 8500 | 10250 | 9700 | 11800 | |
CAPACITY RANGE (L/s) |
|
| |||||||||
MAXIMUM SHIPPING | 1974 |
| 1974 | 2126 |
| 2126 | 2486 | 2486 | 2486 | 2486 | |
WEIGHT (kg) |
|
| |||||||||
|
|
|
|
|
|
|
|
|
| ||
MAXIMUM OPERATING | 1860 |
| 1860 | 2013 |
| 2013 | 2373 | 2373 | 2373 | 2373 | |
WEIGHT (kg) |
|
| |||||||||
|
|
|
|
|
|
|
|
|
| ||
UNIT DIMENSIONS (mm) |
|
|
|
|
|
|
|
|
|
| |
Length (includes hoods) | 3015 | 3117 | 3294 | 3447 | |||||||
Width | 2822 | 2924 | 3101 | 3251 | |||||||
Height | 1824 | 1925 | 2068 | 2118 | |||||||
ROTARY ENERGY |
|
|
|
|
|
|
|
|
|
| |
EXCHANGER |
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
|
|
| Segmented |
|
|
| ||
Size (Diam x Depth) (mm) | 2337 x 76 | 2515 x 76 | 2642 x 76 | 2794 x 76 | |||||||
Nominal Drive Motor kW |
| 0.2 |
| 0.2 | 0.2 | 0.2 | |||||
SUPPLY/EXHAUST FANS |
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
| Backward Inclined, Single Width Single Inlet |
|
| |||||
Drive Type |
|
|
| EC Motor with Integral Frequency Drive |
|
| |||||
Fan Option Code | G, H, J, M, |
| G, H, J, N | H, J, K, N | H, K, J, | K, J, N, P, R | H, K, J, N, P, R | ||||
(see fan option table) | N |
| N, P, R | ||||||||
|
|
|
|
|
|
|
| ||||
FILTERS |
|
|
|
|
|
|
|
|
|
| |
Type |
|
|
|
|
| 51 mm Pleated |
|
|
| ||
Exhaust Air – Qty...Size | 10…508 x 508 x 51 | 8…610 x 610 x 51 | 8…635 x 635 x 51 | 8…635 x 635 x 51 | |||||||
(L x W x D) (mm) | |||||||||||
|
|
|
|
|
|
|
|
|
| ||
Outside Air – Qty...Size | 10…508 x 508 x 51 | 8…610 x 610 x 51 | 8…635 x 635 x 51 | 8…635 x 635 x 51 | |||||||
(L x W x D) (mm) | |||||||||||
|
|
|
|
|
|
|
|
|
| ||
LEGEND |
|
|
|
|
|
|
|
|
|
| |
DWDI — Double Width, Double Inlet |
|
|
|
|
|
|
|
|
| ||
EC — Electronically Commutated |
|
|
|
|
|
|
|
|
|
3