4.3.4 Set Date/Time

Set Date/Time is used to set the date and time of the DataReader. It is important for the user to enter the correct date and time before beginning any operation. When retrieving data files from a Micro-Link 1 Controller, the date and time information are taken from the extracting device (the DataReader or laptop PC).

To display the current date and time, press at the menu prompt. Press again to change the date and time. The date function will appear as Month (MM), Date (DD), Year (YYYY) and Day of the week. Press after entering the correct date and time to confirm the change.

NOTE

Before beginning any operation, ensure that the correct date and time are set in the DataReader. This is impor- tant as the Micro-Link 1 DataCORDER obtains its time from the DataReader. The Micro-Link 2 and Micro- Link 2i use internal clocks.

4.3.5 Power Off

Power Off will switch off power to the unit. Select Power Off and press to turn the power off. To power off from

the main menu, press and hold down at least three seconds.

4.3.6 Micro-Link 1/2/2i

The user will be presented with the following menu selections for the Micro-Link system Controller (not all menu items are valid for the Micro-Link 1). The first two items are displayed on the LCD with the cursor at the first item. To see and select the other items on the menu the user can move the cursor with the up and down arrows to the desired

item. To select the desired item, press .

Extract Data

Command

Display

Figure 4-4. ML2 Menu

a. Extract Data

Extract Data selected from the main DataReader menu will present the user with another menu of available functions

(see Figure 4-4). The user can select the desired function with and .

Extract by Trip

Extract by Date

Last 30 Days

Extract all Data

Figure 4-5. Extract Data Menu

1 Extract By Trip- Valid for ML 2/2i

Allows the user to extract data for the last trip alone, provided a trip marker was set when the last trip was initiated. If

no trip marker is found, then the DataReader will prompt the user to either abort by pressing

or extract all data by

pressing .

2 Extract By Date - Valid for ML 2/2i

Allows the user to extract data within specific dates. Upon selecting the menu, the user is required to enter the begin and the end dates for the data to be extracted.

3 Last 30 Days- Valid for ML 2/2i

Allows the user to extract the last 30 records of data starting from the current date. Normally one day data will constitute one record. In case of multiple records for a single day, the data extracted will only be for the last 30 records.

4-3

62-02575-07

Page 58
Image 58
Carrier Container Refrigeration Unit manual Item. To select the desired item, press

Container Refrigeration Unit specifications

Carrier Container Refrigeration Units are essential components in the logistics and transportation of temperature-sensitive goods. These specialized refrigeration units ensure that perishable items, such as food, pharmaceuticals, and chemicals, maintain their required temperature throughout their journey, whether by sea, land, or air.

One of the primary features of Carrier Container Refrigeration Units is their advanced temperature control capability. These units can easily maintain temperature ranges from -30°C to +30°C, ensuring optimal conditions for various products. This flexibility is crucial for transporting diverse cargo, from frozen foods that require strict low-temperature settings to temperature-sensitive pharmaceuticals that may need to be kept at a steady room temperature.

Moreover, Carrier units are equipped with cutting-edge technologies aimed at improving efficiency and reliability. The use of electronic controls enhances the precision with which temperatures can be set and maintained. Integrated sensors continuously monitor conditions, allowing for real-time adjustments based on external temperature variations or changes in cargo load.

Carrier's eco-friendly refrigerants further underscore the company's commitment to sustainability. These units often utilize low Global Warming Potential (GWP) refrigerants that are less harmful to the environment, aligning with global regulations aimed at reducing greenhouse gas emissions.

Energy efficiency is another hallmark of Carrier Container Refrigeration Units. Many models incorporate high-efficiency compressors and evaporators, resulting in lower energy consumption compared to traditional refrigeration systems. This efficiency not only reduces operational costs but also contributes to a lower carbon footprint, making it an attractive option for environmentally conscious companies.

The design of these refrigeration units prioritizes durability and ease of maintenance. Robust construction materials withstand harsh maritime environments, minimizing the risk of damage during transit. Maintenance-friendly designs ensure that servicing is straightforward and can often be performed with minimal downtime, keeping logistics operations running smoothly.

In summary, Carrier Container Refrigeration Units combine advanced temperature control, energy efficiency, and sustainability with a focus on durability and ease of maintenance. Through innovative technologies and eco-friendly practices, Carrier continues to lead the way in providing reliable refrigeration solutions for the global supply chain, ensuring that temperature-sensitive goods reach their destination safely and efficiently.