1.3 DataCORDER INTERFACE

The DataCORDER is capable of performing the following functions initiated by the DataView Program

1.3.1Data Extraction a. Daily Header Data

Recorded days are presented in the following format:

1. Day 1 date (month, day, year), sensor data, events, ...

2. Day 2 date (month, day, year), sensor data, events, ...

b. Sensor Data

Sensor data will be read based on either standard or generic configuration. Please refer to separately bound manuals covering the Refrigeration Unit for further explanation of standard and generic configurations, see Table 1-2.

1.3.2 Events

Events will be transmitted to the DataCORDER as specified in Table 1-3, Table 1-4 and Table 1-5. The DataCORDER compacts the events, disposing of repetitive events to save memory space. All events have a time and date stamp.

Table 1-3. Temperature Controller Events

Event

When Event Occurs

Data Stored

Limits

 

 

 

 

Set Point Change (SP)

Whenever the temperature

New set point; method

Last 1 per hour, last 6 per

set point changes

used to change it

day.

 

 

Whenever a defrost cycle

Source of initiation (key-

 

Defrost Start (DS)

is initiated and when the

pad, communications, tim-

First 1 per hour, first 10

system is in defrost mode

er, or active from previous

per day.

 

 

at midnight

day)

 

Defrost End (DE)

Whenever a defrost cycle

Source of termination

Last 1 per hour, last 10 per

is terminated

(normal, timer, or HTT)

day

 

 

Whenever Pre-Trip starts

Source of initiation (key-

First 1 per hour, first 4 per

Pre-Trip Start (PS)

pad, communications, or

or is active at midnight

day.

 

active from previous day)

 

 

 

 

 

 

 

Pre-Trip End (PE)

Whenever Pre-Trip com-

Pass/Fail data for each test

Last 1 per hour, last 4 per

pletes.

run since last power up

day.

 

Dehumidification Start

Whenever dehumidifica-

Set point, humidity read-

First 1 per hour, first 10

tion is initiated, or is ac-

ing type (active at mid-

(DHS)

per day.

tive at midnight

night or normal)

 

 

 

 

 

 

Dehumidification End

Whenever dehumidifica-

Set point, humidity read-

Last 1 per hour, last 10 per

(DHE)

tion ends

ing

day

Humidification Start

Whenever humidification

Set point, humidity read-

First 1 per hour, first 10

is initiated, or is active at

ing, method used to cause

(HS)

per day.

midnight or “htESt” is run

it

 

 

 

 

 

 

Humidification End

Whenever humidification

Set point, humidity read-

Last 1 per hour, last 10 per

(HE)

ends

ing

day

Humidity Set Point

Whenever humidity set

New set point, method

N/A

Change

point changes

used to change it

 

 

Case 1: Whenever an

Case 1: Alarms active dur-

Case 1: 1 per hour which

 

is a combination of all

 

alarm changes state

ing this hour

alarm events in that hour

Controller Alarm

 

 

 

 

 

Case 2: At the end of any

 

 

Activity (AL)

 

 

hour where an alarm active

Case 2: Currently active

Case 2: 1 per hour

 

 

during that hour is inactive

alarms

 

 

 

at the end of the hour

 

 

 

 

 

 

Controller S/W Upgrade

Any change in the Con-

New software version

Last 1 per day.

 

troller software revision.

 

 

Container ID Change

Any time the container ID

New ID

Last 1 per day

is changed

 

 

 

62-02575-07

1-6

Page 11
Image 11