Units with Factory-Installed Disconnect — The factory- installed disconnect is an interlocking, door-type. The discon- nect handle locks the door when it is in the ON position. The disconnect handle must be in the OFF position to open the con- trol box door. The disconnect is located in a separate control box behind the control box door for all units. See Fig. 43.

All field wiring must comply with NEC and all local codes. Wire must be sized based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 44 for power wiring con- nections to the unit disconnect and equipment ground.

DISCONNECT SIZE

QUANTITY...MAXIMUM WIRE SIZE

(MCM)

 

200 Amps

1...300

400 Amps

1...600

600 Amps

2...600

Operating Voltage — Operating voltage to the compressor must be within the voltage range indicated on the unit name- plate. Voltages between phases must be balanced within 2%, and the current must be balanced within 10%. See Tables 7-16 for unit electrical data.

Use the following formula to determine the percentage of voltage imbalance.

Voltage Imbalance

=100 x max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60.

 

AB = 452 v

 

BC = 464 v

 

AC = 455 v

 

Average Voltage =

455 + 464 + 455

3

 

=

1371

 

3

=

457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance:

% Voltage Imbalance = 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is be- low the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact local utility immediately.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.