Table 19 — SGC Thermistor Designations
| PIN | FUNCTION AND LOCATION |
| |
THERMISTOR | CONNECTION |
| PART NO. | |
Thermistors | ||||
| POINT |
| ||
|
|
| ||
SAT1 |
|
| ||
J8 – 1,2 (SGC) | underneath the gas heat section |
| ||
|
|
| ||
SAT2 |
|
| ||
J8 – 3,4 (SGC) | underneath the gas heat section |
| ||
|
| HH79NZ033 | ||
SAT3 |
|
| ||
J8 – 5,6 (SGC) | underneath the gas heat section |
| ||
|
|
| ||
LIMTTEMP | J8 – 15,16 (SGC) | Limit Switch Thermistor (LIMTTEMP) — Inserted next the |
| |
lower limit switch |
| |||
|
|
| ||
SGC — Staged Gas Controller |
|
|
Install Unit Accessories — For applications requiring accessories, the following packages are available:
All units:
•barometric relief
•space temperature sensor
•CO2 sensor
•space temperature sensor with CO2
•airflow switch
•filter switch
•smoke detector
All 48ZG,ZT,Z6 units:
•modulating power exhaust
•pressure operated unloaders
All 48ZN,ZW,Z8 units:
•modulating power exhaust
•VFD remote display
Refer to the individual accessory installation instructions in each accessory package for information on installing accessories.
CONTROLS INSTALLATION
Constant Volume (CV) Units — The 48ZG,ZT,Z6 units may be used in applications with additional control features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on installing that accessory. Control options and accessories available for CV units are:
•thermostats
•enthalpy sensor
•enthalpy switch
•relative humidity sensor
•CEM (controls expansion module)
•Navigator™
CONTROL WIRING — The unit can be controlled with a
Install the thermostat according to the installation instruc- tions shipped with the accessory thermostat. Locate thermostat assembly on a solid interior wall to sense average temperature.
Route thermostat cable or equivalent leads of colored wire from subbase terminals through conduit into the low voltage connections in the main control box. For thermostat TB203 connections, see Fig. 67.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger
than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.
Variable Air Volume (VAV) Units — The 48ZN, ZW, Z8 units may be used in applications with additional con- trol features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on in- stalling that accessory. Refer to the Controls and Troubleshoot- ing manual for more information concerning installation and configuration of options and accessories. Control options and accessories available for VAV units are:
•enthalpy sensor
•enthalpy switch
•relative humidity sensor
•CEM (controls expansion module)
•Navigator
•VFD remote display
VAV CONTROL WIRING — The recommended types of control wiring are shown below:
MANUFACTURER | PART NO. | ||
Regular Wiring | Plenum Wiring | ||
| |||
Alpha | 1895 | — | |
American | A21451 | A48301 | |
Belden | 8205 | 884421 | |
Columbia | D6451 | — | |
Manhattan | M13402 | M64430 | |
Quabik | 6130 | — |
SENSORS — Sensors should be wired using single twisted pairs of 20 AWG (American Wire Gage) conductor cable rated for the application, except for the
NOTE: Humidity and CO2 sensors must be powered from isolated
HUMIDITY CONTROL AND HOT WATER AND STEAM VALVES — These devices require 20 AWG twisted pair conductor cables rated for the application for the 4 to 20 mA signal.
SPACE TEMPERATURE SENSOR
CAUTION
Jumper MUST be in place between pins 1 and 3, 3 and 4 or inaccurate readings could result.
To connect the space temperature sensor, see Fig. 68.
59