*NPT plug is field supplied. NOTE: Follow all local codes.
Fig. 58 — Gas Piping Details
Installing Flue/Inlet Hoods — The flue and inlet hoods are shipped in a package taped to the basepan in the fan section. The flue (outlet) hoods are
The hoods are located on the heating section access panel as shown in Fig. 59 (sizes
1.Remove shipping
2.Attach flue outlet hoods (see Fig. 61) to access panel us- ing screws provided. Hoods are placed over each com- bustion outlet.
3.Install flue deflector baffle inside flue deflector hood. See Fig 62 for sizes
4.Inlet hoods are shipped unassembled and must be assem- bled on the access panel (see Fig. 65). Flanges of the hood top and sides should be placed on the inside of the access panel openings. Install hood top and sides with screws provided. Attach speed clips to screen and insert screen into bottom opening of hood. Secure with 3 screws. On large inlet hoods, attach viewport cover over opening in hood (see Fig. 66). Secure with two screws.
•downstream of the heat exchanger cells
•equally spaced as far as possible from the heat exchanger cells
•a duct location where none of the supply air thermistors are within sight of the heat exchanger cells
•a duct location with good mixed supply air portion of the unit.
Table 17 — 48Z Series Staged Gas Implementation
NO. OF |
| MODEL NUMBER POSITION |
|
| POINT |
| HEAT | ||||
STAGES | 3 | 5 |
| 6,7,8 | 10 | HTSTGTYP | CAPMXSTG |
| LIMTHIHT | LIMTLOHT | SIZE |
2 stages | Z | H, K, W, Y |
| 030 | ALL | Default=0 | Default=45 |
| Default=170 F | Default=160 F | Low |
|
|
|
| 035 |
|
|
|
|
|
|
|
|
|
|
| 040 |
|
|
|
|
|
|
|
|
|
|
| 050 |
|
|
|
|
|
|
|
5 stages | Z | J, L, X, Z |
| 030 | ALL | Default=1 | Default=20 |
| Default=170 F | Default=160 F | High |
|
|
|
| 035 |
|
|
|
|
|
|
|
|
|
|
| 040 |
|
|
|
|
|
|
|
|
|
|
| 050 |
|
|
|
|
|
|
|
|
| H, K, W, Y |
| 055 | ALL | Default=1 | Default=20 |
| Default=135 F | Default=125 F | Low |
|
|
|
| 060 |
|
|
|
|
|
|
|
|
|
|
| 070 |
|
|
|
|
|
|
|
|
| H, K |
| 075 | Default=1 | Default=20 |
| Default=135 F | Default=125 F |
| |
|
|
|
| 090 |
|
|
|
|
|
|
|
|
|
|
| G,H,J,K,L,M | Default=1 | Default=20 |
| Default=130 F | Default=120 F |
| |
|
|
|
| 105 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
9 stages | Z | J, L, X, Z |
| 055 | ALL | Default=3 | Default=15 |
| Default=135 F | Default=125 F | High |
|
|
|
| 060 |
|
|
|
|
|
|
|
|
|
|
| 070 |
|
|
|
|
|
|
|
|
| J, L |
| 075 | Default=3 | Default=15 |
| Default=135 F | Default=125 F |
| |
|
|
|
| 090 |
|
|
|
|
|
|
|
|
|
|
| G,H,J,K,L,M | Default=3 | Default=15 |
| Default=130 F | Default=120 F |
| |
|
|
|
| 105 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
|
| LEGEND |
|
|
|
|
|
|
|
| |
CAPMXSTG | — Maximum Capacity per Changes |
|
|
|
|
|
| ||||
HTSTGTYP | — | Heat Stage Type |
|
|
|
|
|
|
|
| |
LIMTHIHT | — Limit Switch Thermistor High Temperature |
|
|
|
|
|
| ||||
LIMTLOHT | — | Limit Switch Thermistor Low Temperature |
|
|
|
|
|
|
56