Carrier 48ZT, ZN030-105, ZW, Z6, Z8075-105 installation instructions Electrical Data, 48ZG,ZN060 Units

Models: Z6 48ZG 48ZT ZW Z8075-105 ZN030-105

1 68
Download 68 pages 19.39 Kb
Page 45
Image 45
Table 12 — Electrical Data, 48ZG,ZN060 Units

Table 12 — Electrical Data, 48ZG,ZN060 Units

NOMINAL

 

COMPR

COMPR

OFM

 

IFM

BASE UNIT

EXHAUST

BASE UNIT WITH

VOLTAGE

NO. 1

NO. 2

 

ONLY

 

 

FAN

EXHAUST FAN

VOLTAGE

 

 

 

 

 

(3 Ph 60 Hz)

RANGE

RLA

LRA

RLA

LRA

Total

Hp

FLA

MCA

 

MOCP

Total

Total

MCA

MOCP

 

FLA

 

Hp

 

FLA

 

 

 

 

 

 

 

 

 

 

 

15

46.2/42

314.9/310.7

 

400/400

10

 

34/30

348.3/340.7

450/400

 

 

 

 

 

 

 

 

15

 

48/44

363.3/354.7

450/450

 

 

 

 

 

 

 

 

 

 

 

 

20

 

62/56

376.6/366.7

450/450

 

 

 

 

 

 

 

20

59.4/54

328.1/322.7

 

400/400

10

 

34/30

361.5/352.7

450/450

 

 

 

 

 

 

 

 

15

 

48/44

376.5/366.7

450/450

 

 

 

 

 

 

 

 

 

 

 

 

20

 

62/56

389.7/378.7

450/450

208/230

187-254

108

506

108

506

26.4

25

74.8/68

343.5/336.7

 

450/400

10

 

34/30

376.9/366.7

450/450

 

15

 

48/44

391.9/380.7

450/450

 

 

 

 

 

 

 

 

 

 

 

 

20

 

62/56

405.1/392.7

500/500

 

 

 

 

 

 

 

30

88.0/80

356.7/348.7

 

450/450

10

 

34/30

390.1/378.7

450/450

 

 

 

 

 

 

 

 

15

 

48/44

405.1/392.7

500/500

 

 

 

 

 

 

 

 

 

 

 

 

20

 

62/56

418.3/404.7

500/500

 

 

 

 

 

 

 

40

114.4/104

384.8/372.7

 

450/450

10

 

34/30

418.2/403.1

500/500

 

 

 

 

 

 

 

 

15

 

48/44

433.2/416.7

500/500

 

 

 

 

 

 

 

 

 

 

 

 

20

 

62/56

445.9/428.7

500/500

 

 

 

 

 

 

 

15

21.0

148.1

 

175

10

 

15.2

163.3

200

 

 

 

 

 

 

 

 

15

 

22.0

170.1

200

 

 

 

 

 

 

 

 

 

 

 

 

20

 

28.0

176.1

200

 

 

 

 

 

 

 

20

27.0

154.1

 

200

10

 

15.2

169.3

200

 

 

 

 

 

 

 

 

15

 

22.0

176.1

225

 

 

 

 

 

 

 

 

 

 

 

 

20

 

28.0

182.1

225

460

414-508

50.6

253

50.6

253

13.2

25

34.0

161.1

 

200

10

 

15.2

176.3

225

 

15

 

22.0

183.1

225

 

 

 

 

 

 

 

 

 

 

 

 

20

 

28.0

189.1

225

 

 

 

 

 

 

 

30

40.0

167.1

 

200

10

 

15.2

182.3

225

 

 

 

 

 

 

 

 

15

 

22.0

189.1

225

 

 

 

 

 

 

 

 

 

 

 

 

20

 

28.0

195.1

225

 

 

 

 

 

 

 

40

52.0

179.4

 

225

10

 

15.2

194.6

225

 

 

 

 

 

 

 

 

15

 

22.0

201.4

250

 

 

 

 

 

 

 

 

 

 

 

 

20

 

28.0

207.4

250

 

 

 

 

 

 

 

15

17.0

114.6

 

150

10

 

12.2

126.8

150

 

 

 

 

 

 

 

 

15

 

18.0

132.6

150

 

 

 

 

 

 

 

 

 

 

 

 

20

 

22.0

136.6

175

 

 

 

 

 

 

 

20

22.0

119.6

 

150

10

 

12.2

131.8

150

 

 

 

 

 

 

 

 

15

 

18.0

137.6

175

 

 

 

 

 

 

 

 

 

 

 

 

20

 

22.0

141.6

175

575

518-632

39.1

176

39.1

176

9.6

25

27.0

124.6

 

150

10

 

12.2

136.8

175

 

15

 

18.0

142.6

175

 

 

 

 

 

 

 

 

 

 

 

 

20

 

22.0

146.6

175

 

 

 

 

 

 

 

30

32.0

129.6

 

150

10

 

12.2

141.8

175

 

 

 

 

 

 

 

 

15

 

18.0

147.6

175

 

 

 

 

 

 

 

 

 

 

 

 

20

 

22.0

151.6

175

 

 

 

 

 

 

 

40

41.0

139.6

 

175

10

 

12.2

151.3

175

 

 

 

 

 

 

 

 

15

 

18.0

157.1

175

 

 

 

 

 

 

 

 

 

 

 

 

20

 

22.0

161.1

200

 

LEGEND

FLA

Full Load Amps

Hp

Nominal Horsepower

IFM

Indoor (Supply) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

NOTE: Units use 2 (low heat) or 3 (high heat) combustion fan motors rated at 0.3 FLA each.

45

Page 45
Image 45
Carrier 48ZT, ZN030-105, ZW, Z6, Z8075-105 installation instructions Electrical Data, 48ZG,ZN060 Units