ZONEKIT2ZCAR

ZONEKIT2ZCAR

WeatherMaker® Two-Zone

Visit www.carrier.com

Installation and Start-Up Instructions

NOTE: Read the entire instruction manual before starting the installation.

This symbol indicates a change since the last issue.

TABLE OF CONTENTS

 

 

PAGE

Safety Considerations

1

Installation Considerations

1

Introduction

1

Installation

1-4

Sequence Of Operation

4-7

Thermostat Wiring

6-8

Care And Maintenance

8

Troubleshooting

9-11

Wiring Diagrams

12-16

Wiring Diagram Notes

16

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for infor- mation or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this prod- uct. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes and wear safety glasses. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local and state building codes and Sheet Metal and Air Conditioning National Association (SMACNA) for special installation require- ments.

Recognize safety information. This is the safety-alert symbolInstallation and Start-Up Instructions . When you see this symbol on the unit or in instructions and manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, or CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.

INSTALLATION CONSIDERATIONS

1. Install in non-condensing area with ambients between 32°F and 150°F.

2.Use vibration isolators (flex connectors) on zone dampers and ductwork to minimize noise.

3.Place dampers away from areas that may be noise sensitive.

4.TXV is required in air conditioning and heat pump applica- tions.

TABLE OF CONTENTSSAFETY CONSIDERATIONS®

COMFORT ZONING SYSTEM

Y2

T'statEqupimt

RC-RH

 

 

 

 

 

 

Y1

HP

Fnc

Jumper

Z￿ C1

 

 

 

 

 

R

Fnc

HP

 

Emergency

o￿

G

Y1

 

3

W1

 

n￿ Op

Y2

W2 DTO

 

Fnc Ht

Heat

e￿

 

 

 

On

1 C

WARNING!

 

C

Off

 

w/oF

 

Z￿C1

 

 

On

 

w/F

 

Off

HOT

parts

 

 

 

 

 

 

 

 

o￿

 

 

 

 

G Y2 Y1 R

 

 

 

 

n￿Op

under this label

 

W1 W2 C

 

24 VAC

e￿

Rev

 

 

 

 

 

 

 

2 C

W1

W2

 

 

Sensors

RC B O Y2 Y1 W1

 

 

W2 G RH

 

HP Duct

 

 

Equipment Term.

 

 

 

 

 

 

 

 

Fig. 1ÐWeatherMaker Two-Zone SystemA97292

(Shown Without Cover)

5.Use separate isolated transformer to supply power to Weath- erMaker Two-Zone Center. (40va minimum, class 2, trans- former, field supplied)

6.Load calculations must be performed to determine equipment size. Equipment selection is matched to block load. It is imperative equipment is not over sized.

7.Ductwork must be designed based off the sum of peak plus 25 percent oversize. It is imperative ductwork is not under sized.

INTRODUCTION

The WeatherMaker Two-Zone System allows the air conditioning and heating equipment to control temperatures in 2 distinct spaces or zones within a building. Each zone has independent temperature settings controlled by a thermostat.

NOTE: Thermostats are purchased separately.

The comfort temperature settings can change automatically through the use of schedules if programmable thermostats are selected. This allows WeatherMaker Two-Zone to change the temperature settings in zones to reflect occupancy or usage. The WeatherMaker Two-Zone System uses motorized air volume control dampers (also called zone dampers) to regulate the flow of conditioned air into the zones.

INSTALLATION

Step 1ÐCheck Equipment and Jobsite

INSPECT EQUIPMENT Ð File claim with shipping company, prior to installation, if shipment is damaged or incomplete.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.