I | Red LEDÐDisplays ON when fan is energized. | |
| ||
J | Red LEDÐDisplays ON when | |
energized. | ||
| ||
K | Red LEDÐDisplays ON when | |
energized. | ||
L | Red LEDÐDisplays ON when reversing valve is ener- | |
gized. |
Red LEDÐDisplays ON when
N | Red LEDÐDisplays ON when |
is energized. |
J2 (Not Shown)ÐCut for 50 hz operation. Lo- O cated under plastic housing approximately 1 in.
above comprotec override.
→ | Table 2ÐTroubleshooting |
| |
|
|
|
|
| LED CODES | ERROR DESCRIPTION | ACTION REQUIRED |
| Green flashes 1 time every sec and no | Normal operation. | None. |
| other LEDs are flashing. | ||
|
|
| |
|
|
| Wait until duct temperature cools below |
| Green flashes 1 time and Red flashes 1 | Duct temperature sensor. | exceeded temperature trip. (Heat leaving |
| air temperature trip limits set at LAT limits | ||
| time | limit exceeded; heat will be locked out. | |
| POT on central control circuit board; range | ||
|
|
| |
|
|
| is 110° to 175°F.) |
| Green flashes 1 time and Red flashes 2 | Duct temperature sensor. | Wait until duct temperature cools below |
| exceeded temperature trip. Range is 105° | ||
| times | heat limit exceeded. | |
| to 155°F. | ||
|
|
| |
| Green flashes 1 time and Red flashes 3 | Duct temperature sensor. | Wait until duct temperature raises above |
| times | limit exceeded; cool will be locked out. | exceeded temperature trip (45°F). |
| Green flashes 1 time and Red flashes 4 | Duct temperature sensor. | Wait until duct temperature raises above |
| times | cool limit exceeded. | exceeded temperature trip (50°F). |
| Green flashes 1 time and Red flashes 5 | HP temperature sensor. | Wait until HP temperature cools below ex- |
| times | limit exceeded; heat will be locked out. | ceeded temperature trip. Fixed at 110°F. |
| Green flashes 2 times and Red flashes 1 | HP temperature sensor error. Second- | Wait until HP temperature cools below ex- |
| time | stage heat limit exceeded. | ceeded temperature trip. Fixed at 105°F. |
| Green flashes 2 times and Red flashes 2 | HP temperature sensor. | Wait until duct temperature raises above |
| times | limit exceeded; cool will be locked out. | exceeded temperature trip (45°F). |
| Green flashes 2 times and Red flashes 3 | HP temperature sensor. | Wait until duct temperature raises above |
| times | limit exceeded. | exceeded temperature trip (50°F). |
| Green flashes 2 times and Red flashes 4 |
| 1. Verify that duct temperature sensor or |
| 1. Duct temperature sensor. | 10k ohm resistor is attached to control cen- | |
| times | 2. Temperature sensor is shorted. | ter at duct temperature connectors. |
|
|
| 2. Replace duct temperature sensor. |
| Green flashes 2 times and Red flashes 5 |
| 1. Verify that duct temperature sensor or |
| 1. Duct temperature sensor. | 10k ohm resistor is attached to control cen- | |
| times | 2. Temperature sensor is open. | ter at duct temperature connectors. |
|
|
| 2. Replace duct temperature sensor. |
| Green flashes 3 times and Red flashes 1 |
| 1. Verify that HP temperature sensor or |
| 1. HP temperature sensor. | 10k ohm resistor is attached to control cen- | |
| time | 2. Temperature sensor is shorted. | ter at HP temperature connectors. |
|
|
| 2. Replace HP temperature sensor. |
| Green flashes 3 times and Red flashes 2 |
| 1. Verify that HP temperature sensor or |
| 1. HP temperature sensor. | 10k ohm resistor is attached to control cen- | |
| times | 2. Temperature sensor is open. | ter at HP temperature connectors. |
|
|
| 2. Replace HP temperature sensor. |
|
|
| 1. Check for short circuits on damper wire |
| Green flashes 3 times and Red flashes 3 |
| connections at the dampers and control |
| Damper fuse blown. | center. | |
| times | 2. Replace damper fuse. | |
|
| ||
|
|
| 3. Check damper operation, may need to |
|
|
| be replaced. |
| Green flashes 3 times and Red flashes 4 | Fatal control center circuit board failure. | Replace control center. |
| times | ||
|
|
| |
|
|
|
|
10