AUTOMATIC TRANSFER SWITCH

AL-CU UL LISTED SOLDERLESS SCREW-TYPE TERMINALS

FOR EXTERNAL POWER CONNECTIONS

 

Normal, Emergency

 

Normal, Emergency

 

& Load Terminals

 

& Load Terminals

Switch Size

Cables

Range of

Switch Size

Cables

Range of

Amps

per Pole

Wire Sizes

Amps

per Pole

Wire Sizes

 

 

 

 

 

 

40-80

 

#8 to 3/0 AWG

800/1000/1200

4

#2 AWG to 600 MCM

100-225

1

#6 AWG to 250 MCM

1600

 

 

260

 

#6 AWG to 350 MCM

2000

8

600 MCM

400

 

#4 AWG to 600 MCM

3000

 

 

 

600

2

#2 AWG to 600 MCM

4000

 

 

NOTES:

*Line and load terminals are located in rear and arranged for bus bar connection.

1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes and number of conductors per pole.

2. Fully rated solid neutral (3x standard normal power connector) provided when required by system voltage.

3. Normal and emergency may be ordered inverted on any switch. Load may be inverted 600-1200 amps. Consult the factory for details.

4. Lug adapters for 3000-4000 amp units may be staggered length for ease of entrance. Consult the factory for details. 5. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact Caterpillar

Information contained in this publication may be considered confidential. Discretion is recommended when distributing.

Materials and specifications are subject to change without notice.

CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate

and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

www.Cat-ElectricPower.com

©2012 Caterpillar

All Rights Reserved.

Printed in U.S.A.

LEHE4651-04 (11/12)

8

Page 8
Image 8
CAT LEHE4651-04 manual Normal, Emergency