AUTOMATIC TRANSFER SWITCH
NEUTRAL SWITCHING
The CTS Series is available in true four pole designs for
SAFE MANUAL OPERATION
The CTS manual operator consists of a large,
Every CTS is provided with an operator inhibit switch to disconnect the electrical drive prior to maintenance. Fully enclosed
TRANSFERRING LARGE MOTOR
OR HIGHLY INDUCTIVE LOADS
Some loads, especially large motors receive severe mechanical stress if power is transferred out of phase while the motor is still rotating. Also, back EMF generated by a motor can result in over currents that can blow fuses or trip circuit breakers. The CTS Series offers four solutions to these problems:
1.Optional Universal Motor Disconnect Contact: This load control disconnects a large motor via its control circuit for an adjustable period of time prior to transfer in either direction. For switching multiple motors, the motor disconnect contact with staged restart disconnects the motors prior to transfer and brings them back on line sequentially.
2.Accessory R50 Phase Monitor: This feature compares the phase angle between both sources of power and prevents transfer until the two are approximately in phase (within a self adjusting range). The CTS’s high speed transfer action coupled with the MX series microprocessor control logic ensure closures at or near zero degree phase difference
3 |
CTS SERIES ATS
400 amp, 2 pole
3.Series CTSD: The CTSD offers a delayed transition on transfer switches 40A and above. This programmed
4.Series CTSCT: Cat closed transition switches combine CTSD operation during a source failure with a highly engineered control system that allows momentary paralleling (100 ms) of two acceptable sources, thereby limiting the impact of transfer on the load. Reference the CTSCT supplement for further details.