11 
3.5.2 Pulse Configuration Registers 
Pulse Repetition  Interval Register  (08)  This read/write register controls the pulse repetition 
interval  and the  state of the output relay.  See Figure 6 for details. 
 08 PRI Register 
Bit 15 14 13 12 11 10  9  8  7  6  5  4  3  2  1  0 
Write OEN Range Not Used PRI Multiplier 
Read OEN Range Not Used PRI Multiplier 
 OEN  Output Relay Enable (1 = enabled/output on) 
 Range  PRI & Delay Range bit 14 13 12 
         0  0  0  25 ns 
         0  0  1  100 ns 
         0  1  0  1 s 
         0  1  1  10 s 
         1  0  0  100 s 
         1  0  1  1 ms 
         1  1  X  invalid 
 PRI Multiplier  PRI Multiplier (period = PRI Multiplier  Range) 
 NOTES: 
 1) The Range  field is used  for both the  PRI and Dela y time setting s. 
 2) The  minimum  programmable  period  is  100  nsec.   Therefore  the minim um PRI 
Multiplier is 4 in the 25 nsec range, and 2 for all other ranges. 
 3) The maxim um PRI M ultiplier i s 1023; t herefore, the  maximum pr ogrammable p eriod 
is 1.023 sec. 
 4) For highest accuracy use the smallest range with a larger multiplier. 
Figure 6.  PRI Register