Page 7
Image 7
Symbology

5.If you are using one extension cord for more than one tool, add the nameplate amperes and use the sum to determine the required minimum cord size.

(See Table A.)

6.If you are using an extension cord outdoors, make sure it is marked with the suffix “W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.

7.Make sure the extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.

8.Protect the extension cords from sharp objects, excessive heat, and damp or wet areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120 VOLT)

NAMEPLATE

EXTENSION CORD

 

LENGTH

 

AMPERES

 

 

25’

50’

75’

100’

150’

(at full load)

 

 

 

 

 

 

 

 

 

 

 

0 – 2.0

18

18

18

18

16

2.1

– 3.4

18

18

18

16

14

3.5

– 5.0

18

18

16

14

12

5.1

– 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1

– 16.0

14

12

10

-

-

16.1

– 20.0

12

10

-

-

-

TABLE A

* Based on limiting the line

voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

 

Canadian Standards Association

 

 

 

Underwriters Laboratories, Inc.

 

 

V~

Volts Alternating Current

A

Amperes

 

 

 

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

SKU 96035

For technical questions, please call 1-800-444-3353.