Chromalox PD441-1 manual Wiring, B.Vertical Position Figure, NOTE When, Installation

Models: PD441-1

1 4
Download 4 pages 55.32 Kb
Page 2
Image 2
B.Vertical Position (Figure 4)

INSTALLATION

6.Heater must not be operated in sludge.

7.Install the heater using a high quality pipe sealing compound on the threads. Screw the heater into the opening (Figure 2). Tighten sufficiently with wrench applied on the hex portion of the screw- plug.

2”

Approx. 6” Cold

place.

A2. Position outlet and inlet in a vertical plane, facing upward to prevent air pockets. Be sure all trapped air is removed from the closed tank. Bleed the air out of the liquid piping system and heater housing prior to operation.

A3. IMPORTANT: Heater should never be located at the highest point in the system. Provide expansion tank, if necessary.

B.Vertical Position (Figure 4)

9.DANGER: Hazard of Fire — Since the heaters are

WARNING: Care must be taken to insure the heated portion does not extend into the coupling area (see Dimensions).

Figure 2 - Exploded View Pipe Insert Heater Mounting

8. Closed Tank Installation

 

NOTE: When

heating

in closed vessels, controls and

back-up controls

must be

used to prevent buildup of temper-

Drip Loop Recommended

to Minimize Passage of

Moisture Along Wiring

Into Terminal Wiring

and Connections

Suitable

Wiring

Locate Drain Pipe

at Bottom of Heater.

Sediment Deposits may be Removed Through Drain Pipe

NOTE: When Outlet

WIRINGManual background Inlet

Maximum Sediment Level.

Install Heater Above

This Level But as Near to it as Possible for Maximum Heated Solution Storage Capacity

ature and/or pressure.

A. Horizontal Position (Figure 3)

Note: In a Forced Circulation System,

Use Pump In Inlet Side

Outlet

Inlet

Heater

Figure 3 - Closed Tank in Horizontal Position

A1. Place heater at an elevation so that natural circulation can take

Figure 4 - Closed Tank in Vertical Position

capable of developing high temperatures, extreme care should be taken to:

A.Avoid contact between heaters and combustible materials.

B. Keep combustible materials far enough away to be free of the effects of high temperatures.

WIRING

WARNING: Hazard of Shock. Any installation involving electric heaters must be effectively grounded in accor- dance with the National Electrical Code.

1.Electric wiring to heater must be installed in accordance with the National Electrical Code and with local codes by a qualified person as defined in the NEC. WARNING: Use copper con- ductors only.

2.When element wattages are not equal, heaters must not be connected in series.

3.Electrical wiring to heater should be contained in rigid con- duit or in sealed flexible hose to keep corrosive vapors and liq- uids out of the terminal housing.

4.If flexible cord is employed, a watertight connector should be used for entry of the cord into the terminal box. Outdoor applica- tions require liquid-tight conduit and connectors.

5.Bring the power line wires through the opening in the terminal box. Connect line wires as shown in the wiring diagram (see Figure 5).

Manual background L-1

L-2

240-480V — Figure 5

Page 2
Image 2
Chromalox PD441-1 manual Wiring, B.Vertical Position Figure, NOTE When, Installation