Step3 Attach the ground lug or ring terminal to the chassis as shown in Figure 10 or Figure 11. For the ground lug, use the
twoscrews with captive locking washers provided. For a ring terminal, use one of the screws provided. Use a number 2
Phillips screwdriver, and tighten the screws to a torque of 8 to 10 in-lb (0.9 to 1.1 N-m).
Figure10 NEBS-Compliant Chassis Ground Connection Using Ground Lug
Figure11 Chassis Ground Connection Using Ring Terminal
Step4 Connect the other end of the ground wire to a grounding point at your site.
4Connect Cables
Warning
Do not work on the system, or connect or disconnect cables during periods of lightning activity. Statement 1001
Warning
Before opening the chassis, disconnect the telephone-network cables to avoid contact with telephone-network
voltages.Statement 1004

System Management Connections

The connections described in Table1 provide system management access.
Table1 System Management Connections

Port Color Connected To: Cable

Console Lightblue PCor ASCII terminal communicationport (usually labeled COM) RJ-45-to-DB-9 adapter cable
Auxiliary Black Modem for remote access RJ-45-to-DB-25 adapter cable
SEE MANUAL BEFORE INSTALLATION
SERIAL 1
SERIAL 0
CONN CONNWIC
2A/S
SEE MANUAL BEFORE INSTALLATION
SERIAL 1
SERIAL 0
CONN CONNWIC
2T
Cisco 2611
100-240V– 1A
50/60 Hz 47 W
W0
AUX
CONSOLE
ETHERNET 0ACT
LINKACTETHERNET 1LINK
W1
36454
Ground lug
103057
SEE MANUAL BEFORE INSTALLATION
SERIAL 1
SERIAL 0
CONN CONNWIC
2A/S
SEE MANUAL BEFORE INSTALLATION
SERIAL 1
SERIAL 0
CONN CONNWIC
2T
Cisco 2611
100-240V– 1A
50/60 Hz 47 W
W0
AUX
CONSOLE
ETHERNET 0ACT
LINK
ACTETHERNET 1LINK
W1
Ring terminal