Adding or Replacing a DC PEM

Wiring a DC PEM

This section provides procedures for connecting a DC PEM to a DC power source.

Preparing to Connect Power and Ground

Follow these steps to prepare the power and ground wires to be connected to the Cisco 10005 DC PEM.

Step 1 Cut the ends of the power and ground wires so that the ends are straight, not slanted.

Step 2 Measure and strip 0.43 inches (11 mm) of insulation off the end of each DC power and ground wire (Figure 4). Trim the end of the insulation so that it is straight, as shown in Figure 4, not slanted.

Figure 4 Stripping Insulation

0.43 in.

(11 mm)

26689

Warning Remove the covering from exactly the specified length of each wire. If you strip too much of the covering, exposed wire protruding from the terminal block will create an electrical hazard. If you strip too little of the covering, the wire might not make a good contact with the terminal, or it might not be held securely in place in the terminal block.

Step 3 Prepare the other end of each wire to be connected to a DC power source according to the requirements of your site.

Step 4 Connect the power and ground wires to the DC power source.

 

Cisco 10005 ESR DC Power Entry Module Installation

12

78-12653-01

Page 12
Image 12
Cisco Systems Cisco 10005 ESR manual Wiring a DC PEM, Preparing to Connect Power and Ground