Adding or Replacing a DC PEM

Step 3 Insert the end of the grounding wire into the grounding receptacle, which is the bottom receptacle in the terminal block on the PEM (Figure 6).

Figure 6 Insert Grounding Wire into Grounding Receptacle

CAUTION: USE

COPPER

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION:

 

QUECONDUCTORS

 

 

 

 

 

 

 

 

 

 

 

N'UTILISEZ

ONLY

 

 

 

 

 

 

 

 

 

 

 

 

DES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUCTEURS EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURVE CAUTION:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BREAKER TERMINALS

MAY BE

 

 

 

 

 

 

 

 

 

 

 

AND

 

ENERGIZED.

 

 

 

 

 

 

 

 

 

 

REMOVE

 

TURN OFF

 

 

 

 

 

 

 

 

 

 

POWERSUPPLY

 

POWER

 

 

 

 

 

 

 

 

 

 

 

BEFORE

 

SOURCE CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

ACCESSING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINALS. GML

THIS

UNIT HAS

CAUTION

 

 

 

 

MORE

 

 

 

 

SUPPLY

THAN ONE

 

POWER CORD.

 

POWER

 

SUPPLYDISCONNECT

 

SERVICING TO

CORDS

 

TWO (2)

 

 

AVOID

 

BEFORE

 

 

 

 

ELECTRIC

SHOCK.

POWER

FAULT

MISWIRE

INPUT -48/60 V 35A

 

53627

Step 4

Ensure that no copper wire strands are left outside the receptacle.

Step 5

Use the screwdriver to tighten the ground screw in the terminal block to a torque

 

of 1.5 to 1.8 newton meters (13.28 to 15.93 inch-pounds). (Tighten in a clockwise

 

direction.) To avoid breaking the screw, do no exceed 2.3 newton meters.

Step 6

Pull on the wire to ensure that it is held firmly in place.

Step 7

Make sure that the other end of the wire is connected to ground at the DC power

 

source.

Step 8

If you are connecting two power sources to the Cisco 10005 ESR, repeat this

 

procedure for the second PEM.

 

 

 

 

Cisco 10005 ESR DC Power Entry Module Installation

 

 

 

 

 

 