NTP-D279 Set Power Monitor Thresholds
Step 6 Review the node information. If you need to make corrections, repeat Steps 3 through 5 to enter the
corrections. If the information is correct, continue with the “NTP-D279 Set Power Monitor Thresholds”
procedure on page 4-8.
Stop.You have completed this procedure.
NTP-D279 Set Power Monitor Thresholds
Step 1 Complete the “DLP-D60 Log into CTC” task on page 3-24 for the node you will set up. If you are
already logged in, continue with Step 2.
Step 2 In node view, click theProvisioning > General > Power Monitor tabs.
Step 3 Tochange the extreme low battery voltage threshold in 0.5 VDC increments, choose a voltage from the
ELWBATVGVdc drop-down menu.
Step 4 To change the low battery voltage threshold in 0.5 VDC increments, choose a voltage from the
LWBATVGVdc drop-down menu.
Step 5 To change the high battery voltage threshold in 0.5 VDC increments, choose a voltage from the
HIBATVGVdc drop-down menu.
Step 6 Tochange the extreme high battery voltage threshold in 0.5 VDC increments, choose a voltage from the
EHIBATVGVdc drop-down menu.
Step 7 Click Apply.
Stop.You have completed this procedure.
Purpose This procedure provisions extreme high, high, extremelow, and low input
battery power thresholds within a –48 volts direct current (VDC)
environment. When the thresholds are crossed, the TCC2 generates
warning alarms in CTC.
Tools/Equipment None
Prerequisite Procedures NTP-D24 Verify Card Installation, page 4-2
Required/As Needed Required
Onsite/Remote Onsite or remote
Security Level Provisioning or higher