QuickSpecs
HP ProLiant DL585 Generation 2 (G2)
Power Specifications
| Part number | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| Operational Input Voltage Range | 90 to 264 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| (Vrms) | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Frequency Range (Nominal) (Hz) | 47 to 63 (50/60) | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Nominal Input Voltage (Vrms) | 100 | 
 | 115 | 208 | 
 | 220 | 
 | 230 | 240 | 
| Max Rated Output Wattage Rating | 910 | 
 | 910 | 1300 | 
 | 1300 | 
 | 1300 | 1300 | 
| Nominal Input Current (A rms) | 11.9 | 
 | 10.2 | 7.7 | 
 | 7.3 | 
 | 6.9 | 6.6 | 
| Max Rated Input Wattage Rating (Watts) | 1163 | 
 | 1148 | 1566 | 
 | 1566 | 
 | 1548 | 1548 | 
| Max. Rated VA  | 1186 | 
 | 1172 | 1598 | 
 | 1598 | 
 | 1579 | 1579 | 
| Efficiency (%) | 80 | 
 | 81 | 83 | 
 | 83 | 
 | 84 | 84 | 
| Power Factor | 0.98 | 
 | 
 | 
 | 
 | 0.98 | 
 | ||
| Leakage Current (mA) | 0.43 | 
 | 0.50 | 0.90 | 
 | 0.96 | 
 | 1.00 | 1.04 | 
| Max. Inrush Current (A peak) | 100 | 
 | 100 | 100 | 
 | 100 | 
 | 100 | 100 | 
| Max. Inrush Current duration (mS) | 
 | 
 | 
 | 
 | 10 | 
 | 
 | 
 | |
NOTE: – To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool
located at url: http://h30099.www3.hp.com/configurator/powercalcs.asp To drill down to calculators:
Click on: "ProLiant Servers"
Click on the Server of interest. Example: DL585 G2
Click on: "Power Calculator" link. (You may need to scroll down to see it)
There are certain 
| Standard Rack Model | Description | 
 | 
| Power Cords / Jumper | 
 | 
 | 
| 
 | ||
| Cords | 
 | |
| 
 | 
 | |
| Optional Country Power | Description | Option Kit Part | 
| Cords and Jumper Cords | 
 | Number | 
| 
 | Nema  | |
| 
 | Nema  | |
| 
 | Nema  | |
| 
 | ||
| 
 | ||
| 
 | ||
| 
 | ||
| 
 | 
| DA - 12575 Canada — Version 37 — May 28, 2008 | Page 40 | 