Status Outputs
The unit contains the following status outputs:
•System OK;
•Setpoint Output; and
•Communications Failure.
Status outputs are FET output to common rated at 30Vdc 500mA.
Connect the output circuit to the appropriate Status Output terminal. Each status output circuit is associated with an LED indicator that lights lit when the digital output is active.
The following table details the status output behavior: |
|
| |
Status Output | LED | LED Status | Description |
System OK active (both modules) | OK | Green | No fault detected |
System OK inactive | OK | Red | • Internal fault detected. |
|
|
| • Supply voltage Low |
|
|
| • Analog Loop supply overloaded |
Setpoint Output | SP | Green | Local setpoint attached to |
Communications Failure | CF | Red | Watchdog alarms active on digital outputs or analog outputs. |
Analog Input
The
Note: The
The analog input has a positive and negative terminal and can be placed at any point in the current loop, providing neither input rises above the 24 volt Analog Loop Supply level.
Each input has a loop resistance of less than 250 ohms and zener diode protection is provided against
A 24Vdc loop supply is available on the
•Analog loop - between an Analog Input
•Positive terminal – i.e., Analog Input (+) to the +24V Analog Loop Supply.
Externally powered loops may be connected by connecting the input between "Analog Input (+)" and “Analog Input