Cooper Lighting IMI-685 Sheet 3 of, Tribute, Installation Instructions, c Slipfitter Mount

Models: IMI-685

1 4
Download 4 pages 40.68 Kb
Page 3
Image 3
Sheet 3 of 4

INSTALLATION INSTRUCTIONS

IMPORTANT : READ CAREFULLY BEFORE INSTALLING FIXTURE.

Tribute

Sheet 3 of 4

1/7/08IMI-685

4c. Slipfitter Mount (FIG. 4c)

The integral slipfitter can be mounted on 2" (2 3/8" O.D.) pipe. Set screws and a thru bolt are provided to clamp it securely to the tenon. Thru bolt will require a drilled hole thru the arm or tenon. Use the slipfitter as a pattern to drill the thru hole. Secure electrical leads from the drill path. Remove slipfitter and clean burrs on tenon from drilled hole. Reinstall the slipfitter. Remove the cover plate from slipfitter and bring leads into compartment. Pull power supply leads and the ground lead into the bottom half of the slipfitter. Be sure the pivot retainer bolt is tightened securely after aiming is accomplished. Tighten all mounting bolts per FIG. 4c.

4d. Trunnion Mount (FIG. 4d)

If the unit is provided with a trunnion which can be mounted directly on a flat surface (Adapters are available for installation on building fronts, poles, crossarms, pipes, etc.) 14-3 SO cable is recommended for making electrical connection. The fixture is provided with a grommnet and a strain relief (approximately 9/16" diameter). To maintain the seal, screws in the strain relief must be retightened whenever the seal is disturbed.

5.Socket Setting Adjustment—Type II or Type III Only (FIG. 5)

Socket is normally factory set to provide IES Type II light distribution pattern. To obtain IES Type III distribution, proceed as follows (FIG. 5).

Loosen the two (2) hex head clamping screws sufficiently for the socket to clear the indexing screws.

Move socket bracket so that the indexing screws engage appropriate indexing holes. See table (FIG. 5) for socket position and resulting light pattern.

FIG. 5

Socket

Mount

Indexing

Indexing

Screw (2)

Hole

Clamping

Screw (2)

FIG. 4c (Slipfitter Mount)

FIG. 5 Pivot Retainer Bolt Torque to 40-50

foot-pounds

 

3/8-16 x 4”

Set screw

Hex HeadThru Bolt

Torque to 15-20

with lock nut.

foot-pounds

 

FIG. 4d (Trunnion Mount)

3/8-16 Bolt

 

3 1/2"

(Torque to 120-140

 

 

[89mm]

inch-pounds)

3" [77mm]

 

2" [51mm]

5 3/8" [137mm]

Mounting

Holes

Light Pattern

Socket Index Position

IES Type

250W Clear HPS Lamp

All other Clear

 

 

(5 3/4” LCL)*

HID Lamps (5” LCL)*

 

II

A

B

III

C

D

NOTE: * Light Center Length.

These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s purpose, please contact your nearest representative.

NOTE: Specifications and dimensions subject to change without notice

Visit our web site at www.cooperlighting.com

Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770.486.4801 ADH070937