C. Assembly of Crown 60/100mm Concentric Venting

(IMPORTANT - Skip to Section D for 80/125mm Concentric Vent Assembly)

WARNING

Failure to follow the instructions could result in flue gas leakage into the combustion air or indoor air, resulting in unsafe or unreliable operation.

Do not lubricate concentric gaskets with anything other than water.

Do not attempt to cut any piping except as permitted in this section. When cutting these

sections, make sure

all cuts are square and allow for proper insertion.

Do not attempt to try to mix this concentric pipe with other venting systems.

1)Concentric vent components supplied with the boiler are packed in a separate carton and include the following:

a)60/100mm elbow adaptor (Crown PN 340509).

b)60/100mm terminal section (straight section with a terminal and overall length of 27 3/4” (Crown PN 230520).

c)Two (2) Rubber wall grommets (Crown PN 230522).

d)Vent gasket and screws for attachment of vent system to boiler.

The 82mm air inlet orifice required for Vent Option 1 is packed in the boiler carton.

The 60/100 straight adaptor is optional equipment. It is supplied with the same screws and gasket as the 60/100 elbow adaptor.

2)Start by attaching the elbow adaptor (or straight adaptor, if used instead) to the top of the boiler using the gasket and four 4.2mm sheet metal screws provided in the vent kit as shown in Figure 7.20. For Vent Option 1, install the 82mm air inlet orifice as shown.

3)If no additional sections of concentric pipe are required, attach the terminal section to the elbow. In most cases, it will need to be cut before doing so. Use the following procedure to cut the pipe:

a)Measure distance “L” from the outside surface of the exterior wall to the end of the elbow as shown in Figure 7.21.

b)Add 2-1/8” to distance “L”. Carefully mark this length on the pipe as shown in Figure 7.22.

c)Press in the two tabs holding the plastic terminal in the terminal section (Figure 7.22). Carefully pull out the terminal and the inner pipe.

d)Cut the outer pipe only at the point marked in Step (b) using aviation shears, a hacksaw, or an abrasive wheel cutter. Be careful to cut the pipe square. De burr the cut end with a file or emery cloth.

e)Cut the plastic inner pipe so that it will protrude 3/8” beyond the outer pipe when reinstalled in the terminal section (Figure 7.23). Use a fine tooth hacksaw or a PVC saw to cut the plastic pipe and be careful to cut the pipe square. De burr the cut edge of the plastic pipe with a file, razor blade, or fine sandpaper.

f)Reinstall the inner pipe in the terminal section. Slip the outside wall grommet over the terminal section and position so that it covers the joint between the outer pipe and the terminal (Figure 7.24).

g)Make a mark on the terminal section 1” from the cut end of the outer pipe as shown in Figure 7.24.

h)Pass the terminal section through the wall from the outside. Push the remaining wall grommet over the terminal section on the inside of the wall. Push the terminal section into the elbow until the mark made in Step

(g) is no longer visible. If necessary, the brown gasket in the inner pipe may be lubricated with a few drops of water.

i)The terminal section must be attached to the elbow with a single #10 x 1/2” sheet metal screw ( not supplied) at the top of the elbow. Drill a 1/8” hole in the location shown in Figure 7.25. Use a short drill bit or a drill stop to ensure that the drill bit does not penetrate the pipe by more than 3/8”. Install a #10 x 1/2” screw in this hole. Do not use a screw longer than 1/2” long.

j)If not already done, make sure that both wall grommets are firmly against the interior and exterior wall surfaces. Seal any cracks or other openings near the terminal through which exhaust could enter the building.

20

Page 22
Image 22
Crown Boiler MWC116ELL, MWC Series, MWC116ENL, MWC116ENT, MWC116ELT manual All cuts are square and allow for proper insertion

MWC116ENL, MWC116ELL, MWC116ELT, MWC116ENT, MWC Series specifications

Crown Boiler's MWC Series represents a commendable choice in the realm of residential and light commercial heating solutions. Specifically, models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL stand out due to their exceptional performance, reliability, and innovative features.

At the core of the MWC Series lies a robust cast iron boiler construction designed to withstand the test of time. This material not only provides durability but also enhances heat retention, thereby increasing the system's efficiency. Each model in this series is designed for natural gas or propane fuel types, ensuring flexibility based on availability and user preference.

A notable feature of the MWC116 models is the efficient heat exchanger, which enables rapid heating of water for both space heating and domestic hot water applications. With a heating capacity of 116,000 BTUs, these boilers deliver ample warmth for mid-sized homes or light commercial settings, making them a versatile option for various applications.

The MWC116ENT model is equipped with an energy-efficient electronic ignition system, which enhances reliability and efficiency. This technology reduces energy consumption, providing users with cost savings on their utility bills. Similarly, the MWC116ELT model boasts an integrated aquastat that regulates water temperature, ensuring optimal performance and comfort.

For those requiring increased venting options, the MWC116ELL model includes advanced horizontal venting capabilities, allowing for flexible installation in various environments. This feature aids in overcoming space limitations and facilitating optimal combustion conditions. The MWC116ENL, on the other hand, features a low NOx emissions configuration, making it an environmentally conscious choice for users concerned about their carbon footprint.

User-friendly controls are a characteristic hallmark of the MWC Series, enabling straightforward operation and easy adjustments. The boilers come equipped with a digital display that provides critical system information and diagnostics, streamlining maintenance efforts.

Overall, the Crown Boiler MWC Series, particularly models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL, offer an impressive blend of efficiency, flexibility, and advanced technology. These units are designed to meet contemporary heating demands while ensuring sustainable operation, making them a wise investment for comfort and performance in residential and light commercial applications alike. With reliable construction and innovative features, the MWC Series remains a top choice for those seeking effective heating solutions.