4.5Installing the Battery Trays (Battery Replacement)
The batteries must be installed and wired to the battery tray prior to installing inside the UPS enclosure.
1.Slide the battery tray out of the UPS.
2.Get the new batteries and install batteries onto the battery tray as shown below.
Battery Jumpers
Wire Strain Relief
Wire Harness (Vo+)
Battery tray mounting hole
Secure harness with cable ties
Wire Harness
Figure 10: Battery Wiring
3.Install the battery clamp using the (4) screws provided. Tighten the screws.
4.Wire the batteries:
a.Add wire jumpers (spade lugs) to interconnect the batteries.
b.Attach the red wire on the wiring harness to the positive terminal (red) of battery.
c.Attach the black wire on the wiring harness to the negative terminal (black) of battery.
d.Secure the harness assembly to the battery clamp with cable ties.
5.Carefully slide the battery tray into the enclosure and secure with the M4 x 8 Truss head screws provided.
Note: The UPS should be secured on the wall/pole before sliding the battery trays into the UPS.
6.Plug the connectorized end of each wiring harness into the receptacle on the front face of the UPS.
Note: For customers who initially ordered
Note: The door must be locked with padlock after installation is complete.
Battery Type | Figure 11: Battery Installation |
The battery is a standard sealed lead acid |
|
battery rated at 12Vdc / 7.2 (7) Ah. When |
|
required, the battery may be replaced with |
|
an approved 12Vdc / 7.2 (7) Ah battery. |
|
Battery Harness Wire
Battery Tray Mounting Screw
Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell batteries collect used batteries for recycling.
© 2010 CyberPower Systems (USA), Inc. All Trademarks are property of their owners. | Page: 10 of 17 |