4.7.2Outdoor Power Cord Selection
1.If an outdoor AC Line cord is selected to connect the unit to AC wall outlet, be sure that the selection criterion in the following table are fully complied.
Cord Rating | Wire (AWG) | Outdoor Use | Attachment Plug | Flexible Cord Type | |
Three conductors, | Check | Use cord type with | 15A, 125V (NEMA | ||
current rating 10A, | specifications of | the suffix "W", | |||
liquid tight cable | or the words "Water | (NEMA | |||
125/250V | gland to determine | resistant" or |
| ||
| SV, SVE, SVO, SVOO, | ||||
| the outside | "Outdoor" marked on |
| ||
|
| SVT, SVTO, SVTOO | |||
| diameter of the | the flexible cord |
| ||
|
| SJ, SJE, SJO, SJOO, | |||
| wire. |
|
| ||
| (O.D. > 6.8mm; |
|
| SJT, SJTO, SJTOO | |
|
|
|
| ||
| 18AWG min. for |
|
| S, SE, SO, SOO, ST, | |
| each inner wire) |
|
| STO, STOO | |
|
|
|
|
|
Table 3: AC Line Cord
2.The connection of the power cord should also be in accordance with Article 110.14 of ANSI/NEPA 70.
3.Using pin terminals (as shown in the Figure 14) for the power cord at the end connected to terminal strip is recommended.
"Warning - Risk of Electric Shock. Connect plug of outdoor power cord only to a covered Class A GFCI receptacle that has an enclosure that is weatherproof with the attachment plug cap inserted or removed."
4. If conduit is used, be sure to choose wires in accordance with the following criterion.
Wire Gauge | Wire Type | Tightening Torque | Minimum temperature | |
(AWG) | rating of conductors | |||
| ||||
Copper conductors | 7 | 75°C | ||
Copper Conductors | ||||
|
|
|
Table 4: Conduit Wires
"Warning - Risk of Electric Shock. Install wires going through conduit only on a circuit protected by a Class A GFCI."
"Warning: Power supply cord must not be attached to the building surface, nor run through walls, ceilings, floors and similar openings in the building structure."
"Warning: The socket outlet shall be installed near the equipment and shall be easily accessible."
"Warning: To reduce the risk of fire, connect the unit only to a circuit provided with Listed 20 Amperes circuit breaker in accordance with the National Electrical Code, ANSI/NFPA."
Note: Wiring, liquid tight fittings, conduit and cable glands shall be selected in accordance with Article 300 of ANSI/NFPA 70.
Note: Before installing the unit, confirm that there is listed IEC
Note: Surge Arrestors or Transient Voltage Surge Suppressor external to the equipment to reduce overvoltages or to bypass surge current shall be installed per Article 280 or 285 of ANSI/NFPA 70.
Note: Be certain to keep coolant or oil away from the unit.