Bradford-White Corp IGE-199R Series Recommended Piping for Power Failure Freeze Protection

Models: IGE-199R Series IGE-199C Series

1 44
Download 44 pages 36.88 Kb
Page 14
Image 14
Recommended Piping for Power Failure Freeze Protection

Recommended Piping for Power Failure Freeze Protection

As long as electrical power and gas are supplied to the EVERHOTwater heater, freeze protection is provided to the heat exchanger and piping inside the water heater with ambient temperatures as cold as -30°F (-34°C), when protected from direct wind exposure. In the event of a power failure at temperatures below freezing, the water heater must be drained of all water to prevent freeze damage. The water heater may be drained manually, or automatically, through the installation of the optional solenoid valves as shown in the following illustration. The drain solenoids are recommended for very cold climates to prevent water heater freeze damage where power failures from ice and windstorms occur.

The electrical connections for the two solenoids must be tied to the 120 volt main power supply terminals provide on the PCB board. When the electrical power to the water heater fails, the ¾” solenoid on the cold water inlet pipe closes, stopping water flow into the water heater. The ¼” solenoid opens, allowing the water heater and connected piping to drain. Make sure the piping from the drain solenoid is run to a suitable drain or outside the building to prevent water damage.

Drain Solenoid Piping (Fig. 3)

Drain Solenoid Piping (Fig. 3) CAUTION

All piping located outside the building must be insulated and wrapped with heat tape to prevent freezing.

14

Page 14
Image 14
Bradford-White Corp IGE-199R Series Recommended Piping for Power Failure Freeze Protection, Drain Solenoid Piping Fig