TO MAKE ELECTRICALCONNECTIONFOR U.S. DRYERS

Reviewelectrical requirements on page 6 of these instructions.

12, For electric dryers:

CONNECTION. The dryer frame is grounded to the neutral conductor

at the terminal block. A 4-WIRE SYSTEMCONNECTIONis required IMPORTANT- All U.S. models are producedfor a 3-WIRE SYSTEM for new or remodeledconstruction,mobile homes, or if local codes do

not permit groundingthrough neutral. If the 4-wire system is used,

the dryer frame cannot be grounded to the neutral conductor at the terminal block. Refer to the following instructionsfor 3- and 4-WIRE

SYSTEM CONNECTIONS.

I

 

/®l _er_

I®

_ _

/

O

,Figure 25

 

B

Removethe terminal block cover plate. (See figure 25.)

II

i

 

A protectiveconduit (plastic)is providedfor the power cord. Cut the

 

 

 

conduit so that it is approximately18 inchesshorterthan the power

 

 

 

cord and thread the power cord through the conduit. (See figures26 &

 

 

 

27.)

 

 

 

Insert the power cord with a U.L. listed strain reliefthrough the hole

Figure 26

 

 

provided in the cabinet near the terminal block. Note, a strain relief

 

 

 

must be used.

 

 

 

3-WIRE SYSTEM CONNECTIONS

 

 

 

Do not loosenthe nuts already installed on the terminal block. Be

 

 

 

sure they are tight. Use a 3/8 inch deep nut driver.

 

 

 

If the power cord hasterminals, place the terminals over the existing

 

 

 

nuts on the posts. The neutral (white or center wire on power cord)

Figure27

 

 

conductormust always be connectedto the center (silver colored)

 

3-Wire System with

post of the terminal block.

 

Secure in place using the nuts provided in the parts oackage. If the

 

Cord Attached

,__,,_Power

 

power cord does not haveterminals, use the cupped washers ahead

 

 

 

of the nuts.

 

 

Ground

Be sure the terminal block nuts are tight. Secure the power cord in

 

 

 

position. Tightenthe strain reliefscrew(s) in order to clamp the strain

 

 

 

reliefto the cord. (See figure 28.)

 

 

 

Replacethe terminal block cover.

 

 

Neutral

BEFOREOPERATINGOR TESTING,follow the grounding directions

 

 

 

on page 5.

 

 

Strain

4-WIRE SYSTEM CONNECTIONS

 

 

relief

Removethe ground strap screw from the terminal block support. Fold

Figure 28

 

 

the ground strap over so both ends of the ground strap are attached

 

 

 

to the center terminal block post.

 

4-Wire System with

Connectthe neutral (white)conductor of the cord to the center (silver)

Power Supply Attached

post of the terminal block. Connectthe grounding (green) wire of the

 

 

 

cord to the terminal block support using the ground strap screw.

--

°

Folded

Connectthe red and black wires of the cord to the outer posts of the

Neutral _

_.'_'_

Ground

terminalBesuretheblockterminal. block nuts are on tight. Secure the power cord in

Post ----. __/

 

Strap

positiOnReplacetotheTightencord.reliefterminal(seeblock, Straincoverfigure. relief29in order.)screw(s)to clamp the strain

///__

 

/e NStraineutral

WARNING: If convertingfrom 4-wire electrical systems to 3-wire,the

 

o _

Relief

ground strap must be reconnectedto terminal block supportto ground

 

(_

4''/

the dryer frame to the neutral conductor.

Figure 29

 

 

Page 15