BUILT–IN CONSTRUCTION DETAILS

BUILT–IN CONSTRUCTION DETAILS

13-3/4"

FIG.04 Bottom of support flange

grill

exhaust

Manual background 3" (to non-combustible construction / minimum lid clearance)

12" (to combustible construction)

10"

2"

22"

1-1/2"

Manual background 25-1/2"

Standard layout for non-combustible enclosure:

10in.2 Min. ventilation on the back side

10in.2 Min. ventilation left hand side

48" Models = 45-3/4" 36" Models = 34-1/2"

18-1/2"

NOTE: If using a backguard apron or rear wall, locate electrical service on the right hand side for rotisserie motor connection

3" Min. for Lid

Clearance

22-3/4"

4" x 4" opening for gas supply line

10-1/8"

35-1/2" Max.

1" Min.

10 in.2 Min. ventilation

on the right hand side

20"

opening for access doors

48" Models = 46"

36" Models = 34"

Layout for insulated jacket only - combustible enclosure:

NOTE: See page 28, #29 for insulated jacket part ordering information.

10in.2 Min. ventilation on the back side

10in.2 Min. ventilation left hand side

11-1/8"

35-1/2"

Max.

1" Min.

48" Models = 51-5/8"

NOTE: If using a backguard apron or rear

36" Models = 40-1/2"

wall, locate electrical service on the right

 

hand side for rotisserie motor connection

 

3" Min. for Lid

 

Clearance

 

23-3/4"

 

4" x 4" opening

18-1/2"

for gas supply line

 

 

3"

20"

10 in.2 Min. ventilation

on the right hand side

 

 

opening for access doors

48" Models = 46"

36" Models = 34"

FIG.04

11

Page 12
Image 12