Step 3: Thread the input cord through the UPS back- | Step 4: Secure the bare cable ends to the UPS terminals | |||||||||||||
plate and secure with the plastic stuffing gland. Ensure |
|
|
| & replace the | ||||||||||
you leave enough free cord to connect to the UPS |
|
|
|
|
|
|
|
| ||||||
|
| terminals. |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Wire Colour |
| Terminal Position |
| UPS Wire Function |
|
| Terminal Wire Size Rating | Tightening Torque | ||||
|
| Green/Yellow Stripe |
| G |
| Input Ground |
|
|
| 2.26Nm |
|
| ||
|
|
|
|
|
|
|
|
| ||||||
|
| Blue |
| N |
| Neutral In |
|
| ||||||
|
|
|
|
|
|
|
| (20 lb in) |
|
| ||||
|
| Brown |
| L |
| Line (Live) In |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
Receiving the Dell UPS
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
NOTE: Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your service representative.
Unpacking the Dell UPS
Remove all parts before beginning the installation. For a complete list of “what’s in the box” either refer to the user guide or visit www.dellups.com
Note that for some Dell UPS models the
CAUTION: Refer to the user guide for complete instructions including important Health & Safety advice.
CAUTION: This equipment is heavy; refer to the user guide for advice on unpacking and safe installation.
Dell UPS Site Preparation Guide, EMEA (230V) | Revision 2, December 2012 |