Dell 5600W, 3750W, 10KW, 4200W Optional 32 Amp, non-locking, 1phase, 3m, UPS Input Cord Kit

Models: 4200W 3750W 5600W 10KW

1 8
Download 8 pages 24.59 Kb
Page 6
Image 6
Optional 32 Amp, non-locking, 1phase, 3m, UPS Input Cord Kit

The following table lists approved AC contactors that can be used as backfeed protection devices for 5600W Online.

Manufacturer

Type

Rating

 

 

 

Moeller GMBH

DILM(C)32-10

600 V, 40A

Tianshui Electrical Aparatus Co. Ltd (E203071)

GSC1(CJX4-d)-4011

220-240 Vac, 42 FLA

 

 

 

LS Industrial Systems Co., Ltd. (E108780)

GMC(D)-32

600 Vac, 45A

 

 

 

The following table lists approved AC contactors that can be used as backfeed protection devices for 10kW.

Manufacturer

Type

Rating

 

 

 

ABB France (E12527)

A75-30

220-240V, 105A

 

 

25 HP at 208V, 30HP at 240V

Tianshui Electrical Aparatus Co. Ltd (E203071)

GSC1(CJX4-d)-6511

220-240 Vac, 68A 25HP

 

 

 

Tianshui Electrical Aparatus Co. Ltd (E203071)

GSC1(CJX4-d)-8011

220-240 Vac, 80A 30HP

 

 

 

Optional 32 Amp, non-locking, 1phase, 3m, UPS Input Cord Kit

If you ordered the optional 32 Amp, non-locking, input cord kit refer to the below drawings for advice on fitting the cable:

Step 1: Remove the cover-plate from the rear of the UPS

Step 2: Remove the back (side nearest cable bare ends)

to access rear-plate terminals and cable access port

of the plastic stuffing gland from the input cord kit

Dell UPS Site Preparation Guide, EMEA (230V)

Revision 2, December 2012

Page 6
Image 6
Dell 5600W, 3750W, 10KW, 4200W installation instructions Optional 32 Amp, non-locking, 1phase, 3m, UPS Input Cord Kit