DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

Safety

CUL and UL Listed and Marked

2.3.2 +24V Standard Power Shelf Configuration(MODUL NAME: ES24/200-JAAxx)

(1)

AC Input:

175VAC ~ 275VAC, 48Amps. Max

(2)

System Capacity:

200Amps. Max.

(3)

Rectifier:

+24V/50A×1~4

(4)Control and Supervisory

Figure 1 shows a front view of shelf.

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

Safety

CUL and UL Listed and Marked

2.3.3 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JBAxx)

(1)

AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2)

System Capacity:

90Amps. Max.

(3)

Rectifier:

-48V/30A×1~3

(4)Control and Supervisory

(5)

Load Distribution:

30A Breaker×5 @ Single Pole

(6)

Low Voltage Disconnect Switch:

100A×1 @ Single Pole at Battery Side

(7)

Battery Breaker:

100A×1

(8)

AC Breaker

 

 

 

 

 

 

2-2

Page 7
Image 7
Delta MCS-1800 manual Environmental Data, Specification Value