DELTA MCS-1800 3U Power Shelf

 

 

 

 

Installation,

Operations and

 

 

 

 

Maintenance Manual

 

 

 

 

 

 

 

 

Settings

 

Description

 

Comment

 

 

 

 

 

 

 

 

 

 

Steps

-

0.1VDC

 

 

 

 

 

AC High Voltage Alarm

 

 

 

 

 

 

 

Function

-

AC high voltage alarm threshold adjustment

 

 

 

 

Default

-

264V

 

 

 

 

 

Recovery

-

261V

 

 

 

 

 

Steps

-

1V

 

 

 

 

 

AC Low Voltage Alarm

 

 

 

 

 

 

 

Function

-

AC Low voltage alarm threshold adjustment

 

 

 

 

Default

-

176V

 

 

 

 

 

Recovery

-

179V

 

 

 

 

 

Steps

-

1V

 

 

 

 

 

Temperature Alarm

 

 

 

 

 

 

 

Function

-

Battery Temperature alarm

 

 

 

 

Default

-

104(40)

 

 

 

 

 

Steps

-

1

 

 

 

 

 

Site ID

 

 

 

 

 

 

 

Function

-

Set identification number for this site

 

 

 

 

Setting

-

4 digits and number range is 0-9

 

 

 

 

Floating / Equalize charging

 

 

 

 

 

 

 

voltage

 

 

 

 

 

 

 

Function

-

Float / Equalize charging voltage

 

 

 

 

Default

-

Float

 

 

 

 

 

 

-

54.3VDC (-48V System)

 

 

 

 

 

-

27.2VDC (+24V System)

 

 

 

 

 

-

EQUALIZE

 

 

 

 

 

 

-

56.4VDC (-48V System)

 

 

 

 

 

-

28.2VDC (+24V System)

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

LVDS Trip Voltage

 

 

 

 

 

 

 

Function

-

Sets LVDS trip voltage

 

 

 

 

Default

-

42VDC (-48V System)

 

 

 

 

 

-

22VDC (+24V System)

 

 

 

 

Recovery

-

When one rectifier work normally and not in the

 

 

 

 

 

 

CL Mode

 

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

Compensation On/Off

 

 

 

 

 

 

 

Function

-

Enable / Disable Temperature Compensation

 

 

 

 

 

 

feature

 

 

 

 

 

Setting

-

ON/OFF

 

 

 

 

 

Default

-

On

 

 

 

 

 

Compensation Volt. Range

 

 

 

 

 

 

 

Function

-

To set Temperature Compensation Voltage

 

 

 

 

Default

-

-1.3VDC~+1.3VDC

(-48V System)

 

 

 

 

 

-

-0.7VDC~+0.7VDC

(+24V System)

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

Equalize Duration Time

 

 

 

 

 

 

 

Function

-

To set the duration of equalizes charging after

 

 

 

 

 

 

AC recovery. This setting is active when battery

 

 

 

 

 

 

deeply discharge resulting from AC fail.

 

 

 

 

Default

-

1-10 hours

 

 

 

 

 

Steps

-

1 hour

 

 

 

 

 

Mains Recovery Charging

-

When mains recovery to avoid the charging

 

 

 

 

Current Limited

 

current too large, CSU will limit the charging

 

 

 

 

 

 

current.

 

 

 

 

 

 

- [ (IL+ Max. Cap.) / Parameter] / available SMR

 

 

 

4-5

Page 20
Image 20