DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Table 1 displays the system input specifications.

Table 1 System Input Specifications

Specification

Value

Nominal range

175 ~ 275VAC

 

90 ~ 275VAC Full Load

Operational range

150V ~ 175Vac de-rating to 80% Load

 

90V ~ 150Vac de-rating to 50% Load

 

50~ 65de-rating 1500W

Frequency

45 ~ 65Hz

Power Factor

>0.99 @ 220VAC, Full Load

THD

<5% @ 220VAC, Full Load

Efficiency

>90% @ 220VAC, Full Load

2.4.2 Output

Table 2 displays the system output specifications.

Table 2 System Output Specifications

 

Specification

Value

 

 

 

 

DC Volts

38~60 VDC (-48V Version)

 

20~30 VDC (+24V Version)

 

 

 

Load regulation

<1%

 

 

 

 

Line regulation

<0.2%

 

 

 

 

Current Limit

110%

 

 

 

 

Current share

<5%

 

 

 

 

Noise:

 

 

Audio band

<2mv

 

Wide band

<10 mVrms

 

Acoustic

<55 dBA

2.4.3 Status/Alarm Indicators

 

The Power Shelf has the following status/alarm indicators:

Load Current

AC ON

Rectifier Fail Alarm (RFA)

Current Limit (CL)

Float/Equalize (FL/EQU)

Major Alarm (MAJ)

Minor Alarm (MIN)

High Voltage Alarm (HV)

High Voltage Shutdown (HVSD)

Low Voltage Alarm (LV)

Low Voltage Disconnect Open (LVDS OPEN)

Fuse Blown (FUSE ALM)

AC Fail (AC FAIL)

2-4

Page 9
Image 9
Delta MCS-1800 manual Output, Status/Alarm Indicators