DELTA MCS-1800 3U Power Shelf

 

 

 

DELTA MCS-1800 3U Power Shelf

 

 

 

Installation, Operations and

 

 

 

Maintenance Manual

 

 

 

 

 

 

 

Settings

Description

 

 

 

 

 

 

FL/EQU

 

 

 

-

Function

- This button is used to manually select SMR into float or equalize state.

 

 

HVSD RST

 

 

 

-

Function

- When SMRs shut down resulting from DC high voltage. This button is

 

 

 

 

used to reset alarm state.

 

 

SMR RST

 

 

 

-

Function

System will detect RFA warning when SMRs are vacant or turned off.

 

 

 

 

However, if the button is pushed at this time, the system will stop

 

 

 

 

sending the warning.

 

 

Voltage/Current

 

 

 

-

Function

This button is used to change the voltage or current of LED display.

 

Notice: When SMR turn off , the system will detect RFA warning in ES48/90-JFAxx. When SMR vacant , the system will detect RFA warning in other system.

4.2.3 Indicators

Table 15 displays the ALU indicators.

Table 15 ALU Indicators

 

Indicator

Color

Function

Description

 

 

 

 

 

 

LED1

Green

FL

System Float State

 

 

 

 

 

 

LED2

Yellow

EQU

System Equalize State

 

LED3

Red

HV

DC High Voltage Alarm-Minor

 

LED4

Red

LV

DC Low Voltage Alarm-Minor

 

LED5

Yellow

MIN

System Minor Alarm

 

 

 

 

 

 

LED6

Red

MAJ

System Major Alarm

 

 

 

 

 

 

LED7

Red

HVSD

High Voltage Shutdown (DC)

 

LED8

Red

AC FAIL

Loss of AC Input

 

LED9

Red

FUSE ALM

DC Output or Breaker SW. Trip

 

 

 

 

 

 

LED10

Red

LVDS OPEN

Low Voltage Disconnect Open

 

 

 

 

 

4.2.4 Relay Output

 

 

 

Table 16 displays the relay output.(Please refer to Figure 5)

Table 16 Relay Output

Relay

Function

Description

Relay

Function

Description

Relay1

ACF

AC Failure

Relay5

LV

DC Low Voltage

Alarm-Minor

 

 

 

 

 

Relay2

MAJ

Major Alarm

Relay6

LVD

Low Voltage Disconnect

Open

 

 

 

 

 

Relay3

HVSD

High Voltage Shutdown

Relay7

FA

Breaker Trip

Alarm

 

 

 

 

 

Relay4

HV

DC High Voltage

Relay8

MIN

Minor Alarm

Alarm-Minor

 

 

 

 

 

4-2

Page 17