DELTA MCS-1800 3U Power Sh elf

Installation, Operations and

Maintenance Manual

3.2.3

Status/Alarm Indicators

 

 

 

Table 11 displays the status alarm indicators

 

Table 11 Status Alarm Indicators

 

 

 

 

 

 

 

 

 

 

Indicator

 

Color

Function

Description

 

 

 

 

 

 

 

 

 

LED

 

Amber

CL

Current Limit

 

 

 

 

 

 

 

 

 

LED

 

Green

AC

AC ON

 

 

 

 

 

 

 

 

 

LED

 

Red

RFA

Rectifier Failure Alarm

 

 

 

 

 

 

 

3.2.4

Mechanical Data

 

 

 

Table 12 displays the rectifier mechanical data.

Table 12 Rectifier Mechanical Data

Dimension

Value

Height

Depth

Width

5.2in. (132mm)

10.35in. (263mm)

3.3in. (83.6mm)

3.3 Operation and Adjustment

All operating adjustments are made at the front panel of each rectifier. The following components are located on each rectifier panel:

1.Float voltage adjustment

2.Current limit adjustment

3.Current test points

4.Alarm indicators

Figure 3 shows different indicators and adjustment points on this unit.

Rectifier adjustments must be done sequentially from the first through the fourth rectifier with AC applied. All adjustments must be made with no load, and the batteries disconnected to ensure adjustment accuracy.

3.3.1 Start-Up

To start up the system, perform the following steps:

1.Aproximately 3 to 8 seconds after the AC applied, the RFA LED extinguishes.

3.3.2Float Voltage Adjustment

Verify the required float voltage setting per battery manufacturer specification. If the factory setting differs from the battery manufacturer recommended setting, the ALU float voltage parameter and each rectifier’s float voltage must be adjusted to the new setting. A digital multimeter and a small screwdriver are required to perform this procedure. Located the float voltage access point (FL) at the front of the rectifier.

To adjust the float voltage, perform the following steps:

1.Remove the ALU.

3-4

Page 14
Image 14
Delta MCS-1800 manual Operation and Adjustment