Delta manual DELTA MCS-1800 3U Power Shelf, Installation, Operations and Maintenance Manual

Models: MCS-1800

1 57
Download 57 pages 45.13 Kb
Page 8
Image 8
Figure 1-1 shows a front view of shelf.

DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Figure 1-1 shows a front view of shelf.

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

2.3.4 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JFAxx)

(1)

AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2)

System Capacity:

90Amps. Max.

(3)

Rectifier:

-48V/30A×1~3

(4)

Control and Supervisory

 

(5)

Load Distribution:

100A Breaker×4 @ Single Pole

(6)

Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side

Figure 1-1 shows a front view of shelf.

 

Environmental Data

 

 

System Environmental Data

 

 

 

 

 

 

Specification

Value

 

 

Operating temperature

0to +50

 

 

Storage temperature

-40to +70

 

 

Humidity

0% to 95% RH

 

 

Altitude

-300 ft. to 10,000 ft.

 

 

Weight

Approximately 48 lbs.

 

 

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

 

 

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

 

 

Seismic

Bellcore GR-63-CORE, Zone 4

 

 

Safety

CUL and UL Listed and Marked

2.4 Electrical Data

The system electrical data is provided in the following tables.

2.4.1 Input

2-3

Page 8
Image 8
Delta DELTA MCS-1800 3U Power Shelf, Installation, Operations and Maintenance Manual, 1 shows a front view of shelf