Troubleshooting

12.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT2 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.1. The Fault indicator will illuminate, indicating the UPS detected a problem.

2.2. An alarm will sound, alerting that the UPS requires attention.

Fault

Example shows UPS on bypass because of output overload, signified by amber load indicator.

AC INPUT

BA

ON

BYPAS S

3.3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

Table 3

Indicator meanings

 

 

LED status

Diagnosis/Audible alarm

All LEDs

 

On bypass due to output overload; beep every half-second

 

 

 

A LED

 

On bypass due to overtemperature condition; beep every 4 sec.

 

 

 

B LED

 

On bypass due to DC bus overvoltage; beep every 4 sec.

 

 

 

C LED

 

DC-DC failure during battery mode; beep every 4 sec.

 

 

 

D LED

 

On bypass due to PFC failure; beep every 4 sec.

 

 

 

E LED

 

On bypass due to inverter failure; beep every 4 sec.

 

 

 

A&C LEDs

 

UPS failed battery test; long beep every minute

 

 

 

C&E LEDs

 

UPS shutdown due to command from communication port (SNMP); no beep

 

 

 

Battery LED Flashing

Internal Battery source not available (continuous horn). Check Battery connection,

completely power down and reboot UPS.

 

 

A&E LEDs

 

Fan locked

 

 

 

B&C

 

REPO active. UPS cannot run with REPO loop open.

 

 

 

B&D

 

UPS is OFF due to previous REPO shutdown. Autorestart disabled.

 

 

 

D&E

 

Charger Malfunction

 

 

 

Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.

If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World- wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.