Liebert GXT2-6000RT230, GXT2-4500RT230 Install the Main Cabinet, Installation and Configuration

Models: GXT2-6000RT230 GXT2-4500RT230

1 40
Download 40 pages 55.97 Kb
Page 14
Image 14

Installation and Configuration

5.0INSTALLATION AND CONFIGURATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.

Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Liebert representative.

! CAUTION

The UPS is heavy (see 13.0 - Specifications). Take proper precautions when lifting or moving it.

Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to 40°C (32 -104°F).

NOTE

UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.

This device is intended for use in an Installation Category II environment.

5.1Install the Main Cabinet

The GXT2 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1Tower UPS Installation

When using the GXT2 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommo- date the additional cabinets (shown below, right).

Figure 5 Tower-use support bases, spacers for external battery cabinets

3U

3U

2U

2U

5U support base for GXT2

Spacers added to support base

End bases and 3U spacer

to accommodate additional battery cabinets

5.1.2Rack-Mount UPS Installation

When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed rails or a shelf.

When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig- ures accompanying 5.1.3 - Installing the Adjustable Rack-MountKit—Sold Separately shows the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.

! CAUTION

Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box is located. The fourth mounting hole is above the Power Distribution Box and is not used.

10

Page 14
Image 14
Liebert GXT2-6000RT230, GXT2-4500RT230 Install the Main Cabinet, Installation and Configuration, Tower UPS Installation