Controls and Indicators
8.0CONTROLS AND INDICATORS
All indicators illuminated for illustration only.
UPStation GXT |
AC INPUT BATTERY UPS ON | BYPASS | ||
|
|
|
|
8.1ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
•ON
•Alarm Silence
•Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the alarm is silenced, the UPStation GXT2 will reactivate the alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from mains power with no alarm conditions present.
•If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24 hours.
•After 24 hours, retest the batteries.
•After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer, Liebert representative or Liebert Worldwide Support Group.
8.2Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions:
Standby and Manual Bypass.
! CAUTION
Pressing the Standby/Manual Bypass button once will transfer the load to bypass power. Pressing the Standby/Manual Bypass button a second time within 4 seconds will cut off power to the output sockets and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.