Liebert GXT2-6000RT230, GXT2-4500RT230 manual Battery run times

Models: GXT2-6000RT230 GXT2-4500RT230

1 40
Download 40 pages 55.97 Kb
Page 34
Image 34

Troubleshooting

Table 6

Battery run times

 

 

 

 

 

 

 

 

 

Load%

4500VA

6000VA

 

 

10%

125

94

 

 

20%

66

46

 

 

30%

41

29

 

 

40%

30

21

Internal Battery

50%

24

17

(minutes)

 

60%

19

13

 

 

70%

16

11

 

 

80%

14

9

 

 

90%

12

8

 

 

100%

10

7

 

 

10%

296

222

 

 

20%

166

124

 

 

30%

114

81

Internal Battery

40%

86

60

50%

70

49

+ 1 External Battery

60%

56

39

Cabinet (minutes)

70%

48

33

 

 

 

 

80%

41

28

 

 

90%

35

24

 

 

100%

31

21

 

 

10%

467

350

 

 

20%

262

197

 

 

30%

180

135

Internal Battery

40%

142

105

50%

120

85

+ 2 External Battery

60%

98

70

Cabinets (minutes)

70%

83

58

 

 

 

 

80%

72

50

 

 

90%

62

43

 

 

100%

54

38

 

 

10%

638

478

 

 

20%

358

269

 

 

30%

247

185

Internal Battery

40%

193

145

50%

164

123

+ 3 External Battery

60%

138

101

Cabinets (minutes)

70%

120

85

 

 

 

 

80%

104

73

 

 

90%

90

63

 

 

100%

80

55

 

 

10%

809

606

 

 

20%

454

341

 

 

30%

313

235

Internal Battery

40%

245

184

50%

208

156

+ 4 External Battery

60%

175

131

Cabinets (minutes)

70%

153

113

 

 

 

 

80%

135

97

 

 

90%

120

85

 

 

100%

106

75

Using the configuration program, the user may specify the number of GXT2-240VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 6 above shows the estimated run times at different loads.