Specifications

13.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

GXT2-6000RT230

 

 

 

 

GXT2-4500RT230

 

Model Rating

6KVA / 4,200W

 

 

 

 

4.5KVA / 3,150W

Dimensions mm (in.)

 

 

 

 

 

 

 

Unit, W x D x H

221 x 547 x 430 (8.7 x 21.5 x 16.9)

 

Shipping, W x D x H

560 x 690 x 500 (22.05 x 27.17 x 19.7)

Weight kg (lbs)

 

 

 

 

 

 

 

Unit

67 (151)

 

 

 

 

67 (151)

 

Shipping

79.5 (175.3)

 

 

 

 

79.5 (175.3)

Input AC Parameters

 

 

 

 

 

 

 

Nominal Operating Frequency

50 or 60Hz (Factory Default = 50)

 

Factory Default VAC

230VAC

 

 

 

User Configurable VAC

220/230/240VAC

 

 

(May be modified using configuration program)

 

 

Operating Voltage Range Without

176 – 276VAC

 

 

 

Battery Operation

 

 

 

 

 

 

 

 

 

 

Maximum Allowable VAC

276VAC

 

 

Input Frequency Without Battery

40 - 70Hz

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

Input Power Connection

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

Output AC Parameters

 

 

 

 

 

 

 

Factory Default VAC

230VAC

 

 

 

Output Connections

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

 

Frequency

50Hz or 60Hz, Nominal

 

Waveform

Sinewave

 

 

 

Main Mode

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

 

Overload

112- 129% for 10 seconds with transfer to bypass

Battery Parameters

 

 

 

 

 

 

 

Type

Valve-regulated, non-spillable, lead acid

 

Quantity x V

20 x 12V

 

 

 

Battery Mfr. / Part #

Yuasa / REW 28-12

 

Back-up Time

See Table 6 - Battery run times

Recharge Time (Internal Batteries)

3 hrs. to 90% capacity after full discharge into 100% load

Bypass Protection Limits

 

 

 

 

 

 

 

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

 

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

 

Disable Bypass operation

When the input frequency prevents synchronous operation

Environmental

 

 

 

 

 

 

 

Operating Temperature

0°C to +40°C (+32°F to +104° F)

 

Storage Temperature

-15°C to +50°C (+5°F to +122° F)

 

Relative Humidity

0-95% non-condensing

 

Operating Elevation

Up to 2000m (6600 ft) at 40

°

C (104

°

F) without derating

 

 

 

 

 

Storage Elevation

15,000m (50,000 ft.) maximum

 

Audible Noise

<55 dBA, at 1 meter from the rear

 

<50 dBA, at 1 meter from the front or sides

 

 

Agency

 

 

 

 

 

 

 

Safety

EN62040-1-1; TUV/GS

 

EMI/EMC/C-Tick EMC

EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive

 

ESD

EN61000-4-2, Level 4, Criteria A

 

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

 

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

 

Surge Immunity

EN61000-4-5, Level 3, Criteria A

 

Transportation

ISTA Procedure 1B

32

Page 36
Image 36
Liebert GXT2-6000RT230, GXT2-4500RT230 manual Specifications, UPS specifications